Inspections for the day of: Monday, July 20, 2009.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-01142 FIRE-Final Inspection7/20/20097/20/20097/20/2009 4:03:04 PMPPART
A temporary occupancy was given until the fire extinguisher is tagged, the thumbturn lock on the main exit is removed (keyed ok) and a sticker is provided as well.
BLD06-02169 FIRE-Final Inspection7/20/20097/20/20097/20/2009 4:00:23 PMPPASS
Life safety passed.
BLD09-00599 FIRE-Final Inspection7/17/20097/20/20097/20/2009 3:59:42 PMPFAIL
Life safety will be ok to pass when the project related fire alarm permit is passed.
FIR09-00400 INSP-Final Inspection7/17/20097/20/20097/20/2009 3:55:45 PMPFAIL
The strobe closest to the exit doors has a short circuit and needs to be replaced and the heat detectors retested and addresses verified.