Inspections for the day of: Friday, July 20, 2012.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00926 FIRE-Final Inspection7/20/20127/20/20127/20/2012 4:17:09 PMPFAIL
The exit signs and emergency lights in the warehouse area need to be finished and tested. Plans need to be resubmitted showing the actual wall layout.
FIR12-00315 INSP-Final Inspection7/20/20127/20/20127/20/2012 3:47:29 PMPPASS
Permit finaled
FIR12-00367 INSP-Sprinkler Rough-in7/20/20127/20/20127/20/2012 3:29:12 PMPPASS
The underground supply piping is ok to cover. Troy was finishing wrapping the galvanized FDC and stated he would also rotate the two outlets to face the street.
FIR12-00363 INSP-Sprinkler Rough-in7/20/20127/20/20127/20/2012 2:42:08 PMPPASS
Underground supply piping ok to cover as marked on the city approved plans with todays date.
FIR12-00343 INSP-Sprinkler Rough-in7/19/20127/20/20127/20/2012 1:25:05 PMPPASS
Sprinkler rough-in passed. One pendant head still needed to be installed. One pendant head shown to be installed in the main level restroom has not been installed and doesn't need to be based on NFPA 13R 6.6.2. Piping can not be covered until the insulation/tenting is completed and inspected. An additional inspection will be required for this.
FIR12-00330 INSP-Sprinkler Rough-in7/19/20127/20/20127/20/2012 12:22:04 PMAPASS
Underground supply piping, as marked on plan, is ok to cover.
FIR12-00342 INSP-Sprinkler Rough-in/Hydro7/19/20127/20/20127/20/2012 11:49:27 AMAPASS
Underground hydro passed with 216 psi on the guage.
BLD12-01812 FIRE-Final Inspection7/19/20127/20/20127/20/2012 11:20:02 AMAPASS
Life safety passed
FIR12-00289 INSP-Sprinkler Rough-in7/19/20127/20/20127/20/2012 10:50:04 AMAPASS
Sprinkler piping is ok to cover
BLD12-00725 FIRE-Final Inspection7/19/20127/20/20127/20/2012 10:28:58 AMAPASS
life safety passed
BLD11-01743 FIRE-Final Inspection7/19/20127/20/20127/20/2012 10:28:18 AMAPASS
life safety passed
BLD12-01369 FIRE-Final Inspection7/19/20127/20/20127/20/2012 9:03:36 AMAPASS
Fire life safety passed. Exit sign has been repaired.
FIR12-00350 INSP-Final Inspection7/19/20127/20/20127/20/2012 8:58:04 AMAPASS
Permit finaled
FIR12-00354 INSP-Final Inspection7/19/20127/20/20127/20/2012 8:29:53 AMAFAIL
Ceiling tile has not be installed yet but piping is ok to cover. Actual suite number is 150.
FIR12-00363 INSP-Sprinkler Rough-in7/19/20127/20/20127/20/2012 8:07:05 AMAFAIL
Underground Inspection failed due to no approved plans on site and I noted that the underground supply piping only has 3'-10" of cover which does not meet the minimum 4'-6" requirement.