ELE13-02254
| ELE-Aging Inspection | 7/20/2016 | 7/20/2016 | 7/22/2016 4:08:05 PM | | CANC |
|
|
|
ELE15-02641
| Electrical Rough-In | 7/20/2016 | 7/20/2016 | 7/20/2016 4:28:35 PM | P | PASS |
|
|
Rooms 602 ; 604 Phone #: ###-#### Inspection requested via web by Kerri Hamilton 602 complete 604 entrance not ready rest of drop lids rough in ok cover
|
ELE16-02297
| Conference | 7/19/2016 | 7/20/2016 | 7/20/2016 3:53:31 PM | P | DONE |
|
|
Jon Phone #: ###-#### Discussed the wiring for garage addition. Free 6" conductor, 1 1/4" on bored holes and securing NM cable, NM support, tamper resistant receptacles, wire size for sub panel, GFCI protection.
|
ELE16-02140
| Electrical Rough-In | 7/19/2016 | 7/20/2016 | 7/20/2016 3:00:30 PM | P | PASS |
|
|
Rough in inspection for walls for cover Contact Steve Hess Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Area turning into a lab. Rough in walls ok cover
|
ELE16-02172
| Electrical Rough-In | 7/19/2016 | 7/20/2016 | 7/20/2016 2:23:00 PM | A | PASS |
|
|
Bill Peace is contact at ###-####. service inspection Phone #: ###-#### Inspection requested via web by Debby Pierce Service rough in ok cover
|
ELE16-02172
| Permanent Service | 7/20/2016 | 7/20/2016 | 7/20/2016 2:22:26 PM | P | PASS |
|
|
Bill Peace is contact at ###-####. service inspection Phone #: ###-#### Inspection requested via web by Debby Pierce p/s u/g n ok
|
ELE16-01612
| Final | 7/19/2016 | 7/20/2016 | 7/20/2016 1:46:19 PM | A | FAIL |
|
|
Lock box code to ofront door is 9701. Call Steve at ###-#### about 30 minutes prior to Inspection Phone #: ###-#### Inspection requested via web by Steve Craig 314.20- Boxes recessed 1/4" or more in wall of non cumbustable material a extension ring shall be installed. wash area tile. 314.25- All boxes shall have covers. Mill work and west of entrance. 314.17- Unused opening in boxes shall be closed. KO seal needed in panel. * Rack system sitting on plug strip.
|
ELE16-02257
| Final | 7/19/2016 | 7/20/2016 | 7/20/2016 1:22:46 PM | A | PASS |
|
|
Final on permanent service Phone #: ###-#### Inspection requested via web by David McClellan Final ok
|
ELE16-00151
| Final | 7/20/2016 | 7/20/2016 | 7/20/2016 12:16:27 PM | P | PASS |
|
|
Remainder of wall rough in inspection for VRT walls. Contact is Eric Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves South 1/2 wall rough in ok cover
|
ELE15-03901
| Electrical Rough-In | 7/19/2016 | 7/20/2016 | 7/20/2016 12:14:13 PM | A | PASS |
|
|
R/I inspection for man cave bathroom hard lid and pre walk final for 7th floor. Call Rafael for inspection. Phone #: ###-#### Inspection requested via web by Rafael Castillo 10th floor bath hardlid rough in ok cover
|
ELE16-01351
| Electrical Rough-In | 7/19/2016 | 7/20/2016 | 7/20/2016 11:19:55 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Office changed to exam rm only at this time. Wall rough in ok cover
|
ELE16-02091
| Electrical Rough-In | 7/19/2016 | 7/20/2016 | 7/20/2016 11:18:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Nurse core A rough in ok cover
|
ELE16-00200
| Final | 7/19/2016 | 7/20/2016 | 7/20/2016 10:39:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL Owner stated they were going to install battery operated smoke detectors. Final ok
|
ELE16-01999
| Final | 7/19/2016 | 7/20/2016 | 7/20/2016 9:42:44 AM | A | NH |
|
|
Inspection requested via web by Clint Tate Doors locked no contact number, posted card.
|
ELE16-02285
| Temporary Service | 7/17/2016 | 7/20/2016 | 7/20/2016 9:22:25 AM | A | PASS |
|
|
Inspection requested via web by TOM BICANDI t/s o/h n ok
|
ELE16-02246
| Final | 7/19/2016 | 7/20/2016 | 7/20/2016 9:05:01 AM | A | FAIL |
|
|
Rosa Phone #: ###-#### 250.52- All available grounding electrodes shall be used for grounding electrode system. Underground water pipe shall be included.
|
ELE16-02246
| Permanent Service | 7/20/2016 | 7/20/2016 | 7/20/2016 9:04:47 AM | P | PASS |
|
|
Rosa Phone #: ###-#### Ground rods in place, must add underground water pipe to grounding electrode system as per 250.52. p/s o/h rec ok
|
ELE16-01943
| Electrical Rough-In | 7/19/2016 | 7/20/2016 | 7/20/2016 8:50:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams S.W. room walls rough in ok cover
|
ELE15-02740
| Electrical Rough-In | 7/19/2016 | 7/20/2016 | 7/20/2016 8:43:21 AM | A | PASS |
|
|
Seth Phone #: ###-#### 1st floor meeting rm and corridor grid rough in ok cover
|
ELE16-01333
| Final | 7/19/2016 | 7/20/2016 | 7/20/2016 8:31:19 AM | A | PASS |
|
|
Dr. Blom// please call before Phone #: ###-#### No card posted. Listing confirmed. Final ok
|