NAF16-00049
| INSP-Conference | 7/19/2016 | 7/20/2016 | 7/20/2016 11:08:25 AM | A | DONE |
|
|
Conference to discuss and walk through life safety requirements. Advised to remove exit sign on delivery door since keyed locked and has sign delivery only, 4 other exit doors exists.
|
NAF16-00023
| INSP-Sprinkler Rough-in | 7/19/2016 | 7/20/2016 | 7/20/2016 10:03:12 AM | A | PART |
|
|
Rough-in inspection of second floor conducted. Hard lid areas (i.e, bathrooms) ok to cover. All mains, branch lines and bracing OK. A few issues are: -uprights spaced within 5' in mechanical room -kennel space shifted so uprights and pendants need to be shifted (see plans) -drop for storage space not cut in -one upright has protector still on
Sprinkler spacing for pendants will need to be verified.
|
GCB15-00145
| FIRE-Conference | 7/20/2016 | 7/20/2016 | 7/20/2016 12:00:00 AM | A | DONE |
|
|
Phone discussion with MJ to discuss if notification devices will need to be tested. Told him yes and he is going to coordinate with hotel for a good time.
When performing this final try to final
GCB12-00032 and NAF16-00044
|