Inspections for the day of: Friday, July 20, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02484 Final7/20/20187/20/20187/20/2018 3:09:28 PMPPASS
Rick Phone #: ###-####...corrections made...ok to final
ELE18-02754 Electrical Rough-In7/20/20187/20/20187/20/2018 2:46:59 PMPPASS
Wall cover Phone #: ###-#### Inspection requested via web by cris flores...south perimeter walls, managers office...ok to cover
ELE18-02179 Conference7/20/20187/20/20187/20/2018 2:31:37 PMPPASS
Talk through rough inspection expectations Phone #: ###-#### Inspection requested via web by Robert Frazier...discussed layout of outlets, stapling, box fill, makeup...full dry sheeting of roof required before wiring...requiring windows be installed before next rough inspection called in along with dry sheeting of roof
ELE18-02749 Conference7/20/20187/20/20187/20/2018 1:38:17 PMPPASS
Hey Tom,

Brian and Dan, the mechanical and plumbing inspectors raised a question in relation to the electrical portion of the installation of a new AC stack in my condo. Would it be possible to ask you a few questions "on-site" before starting the project? Call me (###-####) or Tona (###-####) about 20 to 30 minutes before to be at home.

Thanks! Phone #: ###-#### Inspection requested via web by Nicole Yogerst...discussed location, disconnect, and material used to wire new A/C ...3' requirement infront of disconnect will be met but due to limited space a variance on 30" clearance side to side will be given
ELE17-02649 Final7/19/20187/20/20187/20/2018 12:02:31 PMAPASS
Contact is Andy Chambers. This is another partial final. Phone #: ###-#### Inspection requested via web by Scott Campbell...remaining areas- breeseways, sub steril rm, sterile areas-janitors closet and ANES rm, and patio area...job complete...ok to final permit
ELE18-02484 Final7/19/20187/20/20187/20/2018 10:31:51 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rick Beckman...
1..OCPD for mini split need sized to nameplate rating...max 15A
2..outlets in shop area no power 110.7
3..panel shall be clearly and legible labelled
all circuits in panel
4..all outlets in back warehouse shall have GFCI protection..4 SQ @ panel 210.8(B)
ELE18-02138 Final7/19/20187/20/20187/20/2018 9:49:22 AMAPASS
Phone #: ###-#### Inspection requested via web by BRS Permitting....labelling, OCPD, and disconnect...ok to final
ELE18-02699 Final7/17/20187/20/20187/20/2018 9:26:14 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan...ok to final
ELE18-01983 Final7/19/20187/20/20187/20/2018 9:15:22 AMAPASS
Final for remodel customer will be on site Phone #: ###-#### Inspection requested via web by Matthew White...ok to final
ELE18-02712 Final7/19/20187/20/20187/20/2018 8:53:14 AMAPASS
Dylan...breaker verification; Phone #: ###-####...ok to final
ELE18-02587 Final7/19/20187/20/20187/20/2018 8:28:05 AMAPASS
Contact homeowner half hour before to meet // ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting..
labelling, OCPD, and disconnect ok to final