ELE20-01892
| Electrical Rough-In | 7/20/2020 | 7/20/2020 | 7/20/2020 2:58:31 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Hardlids rough in ok cover
|
ELE20-01379
| Final | 7/20/2020 | 7/20/2020 | 7/20/2020 2:25:07 PM | P | FAIL |
|
|
access code 0917 Phone #: ###-#### Inspection requested via web by Ben Archibald 314.16- Boxes shall have adequate cubic inch space for conductor count installed. 8 cubic inch boxes installed for kitchen island receptacles with 11.25 of conductors installed. 422.30- Double oven shall have a disconnecting means. 110.25 lockouts acceptacle.
|
ELE20-02386
| Temporary Service | 7/20/2020 | 7/20/2020 | 7/20/2020 1:12:05 PM | P | PASS |
|
|
temp pole inspection Phone #: ###-#### Inspection requested via web by ERIC CENTERS t/s u/g n ok
|
ELE20-01869
| Electrical Rough-In | 7/17/2020 | 7/20/2020 | 7/20/2020 10:06:06 AM | A | PASS |
|
|
Grid inspection. Key in lock box on fire extinguisher in hallway. Code 5433 Phone #: ###-#### Inspection requested via web by Dean Gernaat Grid rough in ok cover
|
ELE20-02141
| Electrical Rough-In | 7/17/2020 | 7/20/2020 | 7/20/2020 9:12:30 AM | A | PASS |
|
|
Contact: Andy Eckhart. Underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Service entrance underground complete to electrical room rough in ok cover.
|