Inspections for the day of: Monday, July 20, 2020.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01892 Electrical Rough-In7/20/20207/20/20207/20/2020 2:58:31 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Hardlids rough in ok cover
ELE20-01379 Final7/20/20207/20/20207/20/2020 2:25:07 PMPFAIL
access code 0917 Phone #: ###-#### Inspection requested via web by Ben Archibald 314.16- Boxes shall have adequate cubic inch space for conductor count installed. 8 cubic inch boxes installed for kitchen island receptacles with 11.25 of conductors installed. 422.30- Double oven shall have a disconnecting means. 110.25 lockouts acceptacle.
ELE20-02386 Temporary Service7/20/20207/20/20207/20/2020 1:12:05 PMPPASS
temp pole inspection Phone #: ###-#### Inspection requested via web by ERIC CENTERS t/s u/g n ok
ELE20-01869 Electrical Rough-In7/17/20207/20/20207/20/2020 10:06:06 AMAPASS
Grid inspection. Key in lock box on fire extinguisher in hallway. Code 5433 Phone #: ###-#### Inspection requested via web by Dean Gernaat Grid rough in ok cover
ELE20-02141 Electrical Rough-In7/17/20207/20/20207/20/2020 9:12:30 AMAPASS
Contact: Andy Eckhart. Underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Service entrance underground complete to electrical room rough in ok cover.