Inspections for the day of: Monday, July 21, 2003.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-00813 FIRE-Final Inspection7/15/20037/21/20037/21/2003 12:00:00 AMAPASS
fire life safety finaled 7/21/2003 1:03:24 PM
FIR03-00339 INSP-Final Inspection7/18/20037/21/20037/21/2003 12:00:00 AMAFAIL
brad; Phone #: ###-#### Strobes worked but the horns did not. End of line voltage was checked at 22 volts. Need to also verify batteries 7/21/2003 8:31:16 AM
FIR03-00133 INSP-Supply line flush7/18/20037/21/20037/21/2003 12:00:00 AMAFAIL
Inspection was for rough-in on north wing. See approved plans for areas with deficiencies. 7/21/2003 10:26:55 AM
FIR03-00292 INSP-Sprinkler Rough-in/Hydro7/21/20037/21/20037/21/2003 12:00:00 AMPPASS
rough-in ok. Tenting is ok. Piping is ok to cover. Provide updated asbuilts to city 7/21/2003 4:11:35 PM
FIR03-00326 INSP-Final Inspection7/21/20037/21/20037/21/2003 12:00:00 AMPPASS