FIR04-00223
| INSP-Sprinkler Rough-in/Hydro | 7/15/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/15/2004 at 3:21:43 PM. Contact: ###-####.
|
FIR03-00198
| INSP-Sprinkler Rough-in/Hydro | 7/15/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/15/2004 at 3:24:56 PM. Contact: ###-####.
|
FIR04-00132
| INSP-Sprinkler Rough-in/Hydro | 7/15/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/15/2004 at 3:27:55 PM. Contact: ###-####.
|
BLD04-00525
| FIRE-Final Inspection | 7/19/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dennis Holmes Need to repair exit and add exit sign at corner of main hallway by shop office; add extinguisher as shown on plans and hang another; a slider door was added and needs thumbturn disabled and sign added indicating push to exit 7/21/2004 9:11:22 AM
|
FIR04-00344
| INSP-Final Inspection | 7/19/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/19/2004 at 12:52:30 PM. Contact: ###-####.
|
FIR04-00132
| INSP-Final Inspection | 7/19/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/19/2004 at 5:22:49 PM. Contact: ###-####.
|
FIR04-00303
| INSP-Final Inspection | 7/21/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | FAIL |
|
|
Need updated map of initiating devices; address 110 was used instead of 108 7/21/2004 10:39:53 AM
|
FIR04-00359
| INSP-Final Inspection | 7/20/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | P | FAIL |
|
|
Please call Scott before arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice 7/21/2004 2:22:27 PM One office is 180 sq ft with one head - system is designed 168 sq ft - will need additional head as shown on plans; okay to cover other areas 7/21/2004 2:23:31 PM
|
FIR04-00027
| INSP-Final Inspection | 7/20/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | P | PASS |
|
|
As discussed on the phone 1:00pm if that changes please let me know.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
FIR04-00212
| INSP-Final Inspection | 7/21/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 7/21/2004 at 7:58:34 AM. Contact: ###-####. The demo portion is okay; there are two unit heaters installed and high temp heads will need to be installed 7/21/2004 3:10:17 PM
|
FIR04-00167
| INSP-Sprinkler Rough-in/Hydro | 7/21/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 7/21/2004 at 8:02:13 AM. Contact: ###-####. Rescheduled for per Doug 7/21/2004 3:48:30 PM
|