BLD04-01186
| FIRE-Final Inspection | 7/20/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled. Per the mechanical contractor the hvac unit that servers both spaces 103 and 104 is under 2000cfm. 7/21/2004 9:42:19 AM
|
BLD04-01342
| FIRE-Final Inspection | 7/20/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled. Per the mechanical contractor the hvac unit that servers both spaces 103 and 104 is under 2000cfm. 7/21/2004 9:42:27 AM
|
FIR03-00779
| INSP-Sprinkler Rough-in/Hydro | 7/20/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Hydro test for the wet system passed. Provide forward flush of the backflow preventor per review note #9. Provide signage. Provide alarm interconnections between FACP and new dry pipe riser. Provide head in closet and provide hanger per previous correction notice. 7/21/2004 2:25:31 PM
|
BLD03-02718
| FIRE-Final Inspection | 7/20/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | A | PASS |
|
|
Life safety finaled 7/21/2004 8:21:08 AM
|
FIR04-00268
| INSP-Final Inspection | 7/20/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | P | FAIL |
|
|
Upright sprinkler heads are overspaced in atleast three locations. See plans. Two pendant sprinkler heads are less than 6' apart. See plans. Atleast one armover exceeds 2'. See plans. Inspection was stopped and no other items looked at. These items appear to be existing conditions. Scope of work for the building permit encompasses the entire building therefore the entire sprinkler system shall meet code. Resubmitt plans showing all sprinkler piping, sizing and sprinkler head locations. Show modifications required to meet code. Do not install any more ceiling tile. 7/21/2004 3:35:13 PM
|
BLD04-00046
| FIRE-Final Inspection | 7/21/2004 | 7/21/2004 | 7/21/2004 12:00:00 AM | P | FAIL |
|
|
Project is actually called Wynn's Mill End Fabric. Provide verification to Bill Alexander that the sprinkler system can meet the requirements for the commodities stored. Resubmittals shall meet the requirements of IFC chapter 23. Provide approved door hardware on the second front entry/exit door. Provide sticker as discussed on the main entry/exit with keyed hardware. 7/21/2004 2:03:17 PM
|