Inspections for the day of: Thursday, July 21, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02530 Final7/20/20057/21/20057/21/2005 11:26:12 AMAPASS
tonya Note: does not open intil 10:00 am; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE05-01532 Final7/21/20057/21/20057/21/2005 10:58:40 AMPPASS
Scheduled by a contractor via Hello! on 7/21/2005 at 9:16:36 AM. Contact: ###-####. ok no card
ELE05-01531 Final7/21/20057/21/20057/21/2005 10:58:14 AMPPASS
Scheduled by a contractor via Hello! on 7/21/2005 at 9:15:33 AM. Contact: ###-####. ok no card
ELE05-02396 Rough-In Permanent Service7/21/20057/21/20057/21/2005 10:26:55 AMPPASS
service for new DSL cabinet; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH r/i ok p/s u/g new ok
ELE05-02567 Final7/20/20057/21/20057/21/2005 9:57:26 AMAPART
tonya ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE05-02617 Rough-In Permanent Service7/20/20057/21/20057/21/2005 9:39:11 AMAPASS
travis ###-#### r/i ok called needs a few nail plates and remove low voltage wiring from high voltage 3 gang for fireplace
p/s u/g new ok
ELE05-02497 Permanent Service7/20/20057/21/20057/21/2005 9:04:26 AMANR
please call 30 min prior to inspection//mark; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa conference ok only 250.8 no sms for grds or bonds, bond wire for service conduits shall be sized to T250.66, shall not ID #6 or smaller grd, and if needed run isolated grd per NEC
ELE05-01440 Final7/20/20057/21/20057/21/2005 8:40:18 AMANH
call for access//karen; Phone #: ###-#### or ###-#### Internet Inspection Request from: Letitia Mesa called no answer and wet floors, builder called I tild her only elect. contractor can call for inspection
ELE05-02611 Temporary Service7/20/20057/21/20057/21/2005 8:21:50 AMANR
Phone #: ###-#### Internet Inspection Request from: Tina Payne breaker too high and t/s not grounded called left message
ELE05-02396 Final7/21/20057/21/20057/21/2005 12:00:00 AMPPASS
ok