FIR05-00043
| INSP-Sprinkler Rough-in/Hydro | 7/21/2005 | 7/21/2005 | 7/21/2005 4:09:59 PM | P | FAIL |
|
|
Hanger at last head on SE side is too close to sprinkler upright, missing coverage at front of stair entrance where head is overspaced.
|
FIR05-00308
| INSP-Final Inspection | 7/21/2005 | 7/21/2005 | 7/21/2005 2:43:58 PM | P | FAIL |
|
|
Strobe lens on fire alarm notification devices are below code acceptable height for wall mounted applications.
|
BLD05-00463
| FIRE-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 1:31:29 PM | A | FAIL |
|
|
Emergency lighting and exit signs failed to operate under backup power, no other life safety issues inspected at this time. Contractor to re-schedule when ready.
|
BLD04-02153
| FIRE-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 1:27:31 PM | A | FAIL |
|
|
Provide curb painting at FD access as highlighted on plans and per discussion, verify functionality of main entry/exit mag locks, provide sinage at elevators.
|
FIR05-00262
| INSP-Final Inspection | 7/21/2005 | 7/21/2005 | 7/21/2005 12:33:07 PM | A | FAIL |
|
|
The entire lens of wall mounted strobe devices must be installed between 80" and 96" AFF to meet code requirements, see fire alarm plan review notes.
|
FIR05-00306
| INSP-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 12:28:28 PM | A | PART |
|
|
Work is satisfactory, final pending sign-off on shell permit FIR05-00111.
|
FIR05-00111
| INSP-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 12:25:08 PM | A | FAIL |
|
|
Provide foreward flow test of backflow preventer, provide NFPA25, attatch calc. sticker, install missing escutcheon at riser room, sinage to indicate areas controled by system control valves.
|
FIR04-00749
| INSP-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 12:19:21 PM | A | PASS |
|
|
Underground fire supply permit finaled.
|
FIR05-00408
| INSP-Sprinkler Rough-in/Hydro | 7/20/2005 | 7/21/2005 | 7/21/2005 12:17:17 PM | A | PART |
|
|
Overhead rough-in is satisfactory. Will final permit when ceiling tile and escutcheons are installed.
|