Inspections for the day of: Thursday, July 21, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Kinnear
TitleELE-INSPECTOR
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02616 Final7/20/20057/21/20057/21/2005 4:30:16 PMAFAIL
Al ###-#### needs to cover s cord to protect from traffic. needs lable for j-box.
ELE05-02473 Rough-In Permanent Service7/21/20057/21/20057/21/2005 4:27:33 PMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok cover ri p/s o/h n ok
ELE05-02628 Electrical Rough-In7/21/20057/21/20057/21/2005 4:26:12 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook ok cover ri
ELE05-02534 Electrical Rough-In7/21/20057/21/20057/21/2005 3:29:30 PMPPASS
Scheduled by a contractor via Hello! on 7/21/2005 at 6:58:08 AM. Contact: ###-####. ok conf with electrician regarding rack for high voltage j boxs
ELE05-02532 Electrical Rough-In7/20/20057/21/20057/21/2005 3:28:10 PMPPASS
Scheduled by a contractor via Hello! on 7/20/2005 at 4:45:49 PM. Contact: ###-####. ok cover walls only
ELE04-03204 Final7/20/20057/21/20057/21/2005 3:24:37 PMPPASS
margie-- ###-####--call 1st before insp ok final note gfci in kitchen will not reset owner was there & she will take care of it
ELE05-02627 Electrical Rough-In7/21/20057/21/20057/21/2005 3:23:22 PMPPASS
trench cover//richard ###-#### ok cover under ground cable
ELE04-03788 Permanent Service7/21/20057/21/20057/21/2005 3:22:15 PMPPASS
Scheduled by a contractor via Hello! on 7/21/2005 at 9:08:19 AM. Contact: ###-####. p/s u/g n ok
ELE05-02609 Electrical Rough-In7/20/20057/21/20057/21/2005 11:06:15 AMANR
Trench inspection after 9:00 am. Heron Cove condo complex landscape lighting. River Run and River Park crossroads.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot trench not ready -- note conf with electrician. -- pole base conduit not deep enough for nec table 300.5. uf cable pulled in pvc conduit not approved
ELE05-02447 Temporary Service7/20/20057/21/20057/21/2005 11:00:41 AMAPASS
robert; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g n ok
ELE05-01529 Rough-In Permanent Service7/20/20057/21/20057/21/2005 9:55:34 AMAPASS
Scheduled by a contractor via Hello! on 7/20/2005 at 9:42:17 AM. Contact: ###-####. ok cover ri p/s u/g n ok
ELE05-01879 Final7/21/20057/21/20057/21/2005 8:36:30 AMAPASS
bob ###-#### Internet Inspection Request from: Bob Glenn ok final
ELE04-03788 Electrical Rough-In7/20/20057/21/20057/21/2005 8:17:40 AMAPASS
Scheduled by a contractor via Hello! on 7/20/2005 at 11:18:20 AM. Contact: ###-####. ok cover anop
ELE05-00514 Final7/19/20057/21/20057/21/2005 8:09:40 AMAPASS
ken heller-- ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok final
ELE05-01856 Final7/21/20057/21/20057/21/2005 7:17:04 AMAPASS
bob ###-#### mike this is the one that has part on it but final is ok Internet Inspection Request from: Bob Glenn ok final