FIR06-00255
| INSP-Final Inspection | 7/20/2006 | 7/21/2006 | 7/21/2006 3:49:49 PM | A | FAIL |
|
|
Inspection was not for a final but for a cover inspection for the hard lid areas. These areas are ok to cover.
|
FIR06-00452
| INSP-Sprinkler Rough-in | 7/20/2006 | 7/21/2006 | 7/21/2006 2:57:54 PM | A | PASS |
|
|
See marked plans for more areas that the sprinkler piping is ok to cover.
|
FIR06-00259
| FIR-Aging Inspection | 7/21/2006 | 7/21/2006 | 7/21/2006 2:48:10 PM | | NR |
|
|
Per Greg the work is in progress.
|
BLD05-03072
| FIRE-Final Inspection | 7/21/2006 | 7/21/2006 | 7/21/2006 2:43:07 PM | P | FAIL |
|
|
Still need the fire alarm permit finaled. Life safety for the shell and Sign Company tenant is ok for a temporary occupancy once the fire alarm is a go. The south tenant work is ongoing at this time.
|
BLD05-03243
| FIRE-Final Inspection | 7/21/2006 | 7/21/2006 | 7/21/2006 2:42:48 PM | P | FAIL |
|
|
Still need the fire alarm permit finaled. Life safety for the shell and Sign Company tenant is ok for a temporary occupancy once the fire alarm is a go. The south tenant work is ongoing at this time.
|
BLD05-01262
| FIRE-Final Inspection | 7/21/2006 | 7/21/2006 | 7/21/2006 2:42:29 PM | P | FAIL |
|
|
Still need the fire alarm permit finaled. Life safety for the shell and Sign Company tenant is ok for a temporary occupancy once the fire alarm is a go. The south tenant work is ongoing at this time.
|
FIR06-00218
| INSP-Final Inspection | 7/20/2006 | 7/21/2006 | 7/21/2006 2:40:56 PM | A | FAIL |
|
|
Still need to hydro test the FDC and connect/test the alarms. Forward flush passed. The rough-in for the south tenant failed due to numerous obstructions to the upright sprinkler heads by duct work.
|
MIS06-00170
| FIR-Final | 7/21/2006 | 7/21/2006 | 7/21/2006 1:22:01 PM | P | PART |
|
|
A temporary occupancy was given until the fire extinguisher is mounted and tagged as discussed. Provide battery backup for the exit signs and remount the address. Per Ron Hill this was reviewed under the UBC and the occupant load does not require emergency lighting to be installed.
|
FIR06-00218
| INSP-Sprinkler Rough-in/Hydro | 7/20/2006 | 7/21/2006 | 7/21/2006 12:40:33 PM | A | PASS |
|
|
Above ground hydro test passed. Still need to hydro the remote FDC.
|
MIS06-00176
| FIR-Final | 7/20/2006 | 7/21/2006 | 7/21/2006 12:39:41 PM | A | PASS |
|
|
Life safety finaled
|
MIS06-00184
| FIR-Final | 7/20/2006 | 7/21/2006 | 7/21/2006 9:52:25 AM | A | FAIL |
|
|
Repair exit signs, repair emergency lights, mount and tag fire extinguishers and provide annual inspection for the fire sprinkler riser
|
BLD06-00531
| FIRE-Final Inspection | 7/20/2006 | 7/21/2006 | 7/21/2006 8:58:20 AM | A | FAIL |
|
|
Provide the correct sticker for the door, provide the additional exit sign and exit discharge lighting as noted on the approved plans
|
BLD05-03475
| FIRE-Final Inspection | 7/20/2006 | 7/21/2006 | 7/21/2006 8:56:20 AM | A | PASS |
|
|
Fire life safety for the shell is passed.
|
FIR06-00452
| INSP-Sprinkler Rough-in | 7/19/2006 | 7/21/2006 | 7/19/2006 4:32:59 PM | A | CANC |
|
|
Mike is the contact @ ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
|