Inspections for the day of: Monday, July 21, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-03247 FIRE-Final Inspection7/21/20087/21/20087/21/2008 4:36:10 PMPPASS
Fire life safety finaled.
FIR07-00524 INSP-Final Inspection7/21/20087/21/20087/21/2008 4:35:28 PMAFAIL
See annotations on approved plan set for locations of areas or items in need of correction including 3rd floor MP stations, dB levels at ADA bathrooms and one staff restroom, two non-functional notification devices, PIV tamper self restoring signal per note #7, fire alarm interconnection to the mag locks at the main entry/exit doors, provide map at the panel per review note #24. FACP batteries, phone lines, sd, HD at the mech. room, sprinkler riser supervision, elevator controls with the exception of hoistway devices and voltage monitoring all tested okay.
BLD08-01018 FIRE-Final Inspection7/21/20087/21/20087/21/2008 1:53:47 PMAFAIL
Need to repair three non-functional exit signs, post the fire extinguisher, provide approved hardware at the back exit and main entry/exit doors (main exit needs "door to remain unlocked while building is occupied" signage), EM lights tested okay.
BLD07-03026 FIRE-Final Inspection7/18/20087/21/20087/21/2008 11:25:07 AMAPASS
Noted deficiencies repaired, fire life safety finaled.
BLD07-03027 FIRE-Final Inspection7/18/20087/21/20087/21/2008 11:23:14 AMAPASS
C/N items are finished, fire life safety passed final inspection.
FIR08-00068 INSP-Final Inspection7/20/20087/21/20087/21/2008 11:22:29 AMAPASS
Required corrections verified for compliance, fire sprinkler permit finaled.
FIR08-00066 INSP-Final Inspection7/20/20087/21/20087/21/2008 11:21:31 AMAPASS
Correction notice items are complete, final fire sprinkler inspection passed, permit finaled.