BLD05-03247
| FIRE-Final Inspection | 7/21/2008 | 7/21/2008 | 7/21/2008 4:36:10 PM | P | PASS |
|
|
Fire life safety finaled.
|
FIR07-00524
| INSP-Final Inspection | 7/21/2008 | 7/21/2008 | 7/21/2008 4:35:28 PM | A | FAIL |
|
|
See annotations on approved plan set for locations of areas or items in need of correction including 3rd floor MP stations, dB levels at ADA bathrooms and one staff restroom, two non-functional notification devices, PIV tamper self restoring signal per note #7, fire alarm interconnection to the mag locks at the main entry/exit doors, provide map at the panel per review note #24. FACP batteries, phone lines, sd, HD at the mech. room, sprinkler riser supervision, elevator controls with the exception of hoistway devices and voltage monitoring all tested okay.
|
BLD08-01018
| FIRE-Final Inspection | 7/21/2008 | 7/21/2008 | 7/21/2008 1:53:47 PM | A | FAIL |
|
|
Need to repair three non-functional exit signs, post the fire extinguisher, provide approved hardware at the back exit and main entry/exit doors (main exit needs "door to remain unlocked while building is occupied" signage), EM lights tested okay.
|
BLD07-03026
| FIRE-Final Inspection | 7/18/2008 | 7/21/2008 | 7/21/2008 11:25:07 AM | A | PASS |
|
|
Noted deficiencies repaired, fire life safety finaled.
|
BLD07-03027
| FIRE-Final Inspection | 7/18/2008 | 7/21/2008 | 7/21/2008 11:23:14 AM | A | PASS |
|
|
C/N items are finished, fire life safety passed final inspection.
|
FIR08-00068
| INSP-Final Inspection | 7/20/2008 | 7/21/2008 | 7/21/2008 11:22:29 AM | A | PASS |
|
|
Required corrections verified for compliance, fire sprinkler permit finaled.
|
FIR08-00066
| INSP-Final Inspection | 7/20/2008 | 7/21/2008 | 7/21/2008 11:21:31 AM | A | PASS |
|
|
Correction notice items are complete, final fire sprinkler inspection passed, permit finaled.
|