FIR08-00724
| INSP-Final Inspection | 7/21/2009 | 7/21/2009 | 7/27/2009 1:27:17 PM | P | PASS |
|
|
Fire alarm finaled.
|
FIR09-00171
| INSP-Conference | 7/21/2009 | 7/21/2009 | 7/21/2009 5:09:13 PM | P | DONE |
|
|
Regarding site inspection schedule.
|
FIR09-00371
| INSP-Conference | 7/21/2009 | 7/21/2009 | 7/21/2009 5:08:22 PM | P | DONE |
|
|
Regarding project inspection schedule.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 7/21/2009 | 7/21/2009 | 7/21/2009 5:06:47 PM | P | NR |
|
|
Rack system trip tests and overhead hydrostatic tests not ready. Rough-in inspection completed for system #27.
|
FIR09-00370
| INSP-Sprinkler Rough-in | 7/20/2009 | 7/21/2009 | 7/21/2009 2:31:38 PM | P | FAIL |
|
|
Pendent head at the storage room is overspaced, two hangers at office 412 are beyond max. spacing to heads on systems over 100 psi. See red line annotations on stamped plan set and circled items # 19 and 22 on FP1 under general notes for details.
|
FIR09-00347
| INSP-Sprinkler Rough-in/Hydro | 7/21/2009 | 7/21/2009 | 7/21/2009 1:51:38 PM | P | PART |
|
|
Remainder of underground fire supply line piping okayed for cover-see initialed red line annotations on approved plans.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 7/16/2009 | 7/21/2009 | 7/21/2009 12:45:38 PM | A | PART |
|
|
Continuiong rough in inspections and hydro tests. Please call with time frame. Phone #: ###-#### Internet Inspection Request from: Jeff Packham
|
FIR08-00724
| INSP-Final Inspection | 7/17/2009 | 7/21/2009 | 7/21/2009 12:44:46 PM | A | PART |
|
|
Remainder of alarm devices tested okay, final pending repair of loop two ground fault.
|
FIR09-00197
| FIR-Aging Inspection | 7/21/2009 | 7/21/2009 | 7/21/2009 12:39:47 PM | | DONE |
|
|
Work in progress.
|
BLD09-00598
| FIRE-Final Inspection | 7/20/2009 | 7/21/2009 | 7/21/2009 12:38:57 PM | A | PASS |
|
|
Fire life safety passed.
|
FIR08-00441
| INSP-Final Inspection | 7/20/2009 | 7/21/2009 | 7/21/2009 12:38:16 PM | A | PASS |
|
|
Re-inspection for noted deficiencies passed, fire sprinkler permit finaled.
|
BLD09-01186
| FIRE-Final Inspection | 7/20/2009 | 7/21/2009 | 7/21/2009 12:37:13 PM | A | PASS |
|
|
Fire life safety inspection completed acceptable.
|
FIR09-00347
| INSP-Sprinkler Rough-in/Hydro | 7/21/2009 | 7/21/2009 | 7/21/2009 8:29:47 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 7/21/2009 at 8:27:36 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 21 2009 8:29AM.
|