BLD14-01245
| FIRE-Final Inspection | 7/21/2014 | 7/21/2014 | 7/21/2014 3:24:45 PM | P | PASS |
|
|
Life safety passed
|
FIR14-00280
| INSP-Final Inspection | 7/21/2014 | 7/21/2014 | 7/21/2014 3:14:37 PM | P | PART |
|
|
2nd floor only fire sprinkler work is complete
|
BLD14-01373
| FIRE-Final Inspection | 7/21/2014 | 7/21/2014 | 7/21/2014 2:38:03 PM | P | PASS |
|
|
Life safety passed
|
FIR14-00370
| INSP-Final Inspection | 7/21/2014 | 7/21/2014 | 7/21/2014 2:05:51 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00055
| INSP-Alarm Testing | 7/9/2014 | 7/21/2014 | 7/21/2014 2:05:27 PM | A | DONE |
|
|
The existing duct smoke detectors did not shut down upon detection of smoke. The new duct smoke detectors are not connected to the fire alarm panel. Need the correct orfice in the inspectors test line so that the flow switch can be tested. All other items tested ok.
|
FIR14-00370
| INSP-Alarm Testing | 7/9/2014 | 7/21/2014 | 7/21/2014 10:47:04 AM | A | DONE |
|
|
Dale Phone #: ###-####
|
BLD14-01846
| FIRE-Final Inspection | 7/21/2014 | 7/21/2014 | 7/21/2014 9:51:31 AM | A | PASS |
|
|
Life safety passed. Thumbturn deadbolt to be removed prior to building sign off as discussed.
|
BLD14-00942
| FIRE-Final Inspection | 7/18/2014 | 7/21/2014 | 7/21/2014 9:50:51 AM | A | PASS |
|
|
Life safety passed
|