Inspections for the day of: Monday, July 21, 2014.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-01245 FIRE-Final Inspection7/21/20147/21/20147/21/2014 3:24:45 PMPPASS
Life safety passed
FIR14-00280 INSP-Final Inspection7/21/20147/21/20147/21/2014 3:14:37 PMPPART
2nd floor only fire sprinkler work is complete
BLD14-01373 FIRE-Final Inspection7/21/20147/21/20147/21/2014 2:38:03 PMPPASS
Life safety passed
FIR14-00370 INSP-Final Inspection7/21/20147/21/20147/21/2014 2:05:51 PMPPASS
Permit finaled
FIR14-00055 INSP-Alarm Testing7/9/20147/21/20147/21/2014 2:05:27 PMADONE
The existing duct smoke detectors did not shut down upon detection of smoke. The new duct smoke detectors are not connected to the fire alarm panel. Need the correct orfice in the inspectors test line so that the flow switch can be tested. All other items tested ok.
FIR14-00370 INSP-Alarm Testing7/9/20147/21/20147/21/2014 10:47:04 AMADONE
Dale Phone #: ###-####
BLD14-01846 FIRE-Final Inspection7/21/20147/21/20147/21/2014 9:51:31 AMAPASS
Life safety passed. Thumbturn deadbolt to be removed prior to building sign off as discussed.
BLD14-00942 FIRE-Final Inspection7/18/20147/21/20147/21/2014 9:50:51 AMAPASS
Life safety passed