Inspections for the day of: Tuesday, July 21, 2015.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00542 ELE-Aging Inspection7/21/20157/21/20157/21/2015 2:57:18 PM CANC
too busy
ELE13-00835 ELE-Aging Inspection7/21/20157/21/20157/21/2015 2:56:38 PM CANC
too busy
ELE13-01374 ELE-Aging Inspection7/21/20157/21/20157/21/2015 2:55:27 PM CANC
Too busy
ELE15-02240 Rough-In Permanent Service7/20/20157/21/20157/21/2015 2:37:51 PMPPASS
Need ok for Idaho Power to turn service back on Phone #: ###-#### Inspection requested via web by Randy Fletcher Service change only rough in ok. p/s u/g rec ok
ELE15-01776 Electrical Rough-In7/21/20157/21/20157/21/2015 2:16:41 PMPPASS
Thank you Phone #: ###-#### Inspection requested via web by Eric Brown Patio cover rough in ok cover.
ELE15-01824 Electrical Rough-In7/20/20157/21/20157/21/2015 1:37:07 PMPPASS
We are requesting a ceiling rough-in inspection for tomorrow 7/21/15 in the afternoon. Our onsite contact is Rich @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Check disconnecting means located in ceiing of focus room for a transfomer located on other side of new wall is with in sight of transformer it serves. Grid in focus, security, and IT rooms rough in ok cover
ELE15-02247 Final7/21/20157/21/20157/21/2015 1:03:33 PMPFAIL
Contact is Jon Fivecoat at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce See permenant service.
ELE15-02247 Permanent Service7/21/20157/21/20157/21/2015 12:59:52 PMPFAIL
Contact is Jon Fivecoat at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce BCC 4-05-32- Code violations not to be retained.
200.6- Grounded conductor shall be identified with white.
250.50- All available grounding electode systems shall be used. Metal water pipe.
250.134-Concentic broken out in bot of panel. Shall be repaired.
230.24-Overhead service mast shall be secured in place.
ELE15-02225 Final7/21/20157/21/20157/21/2015 12:56:00 PMPCANC
Phone #: ###-#### Inspection requested via web by daniel bibikov Needed rough in inspection
ELE15-02225 Electrical Rough-In7/21/20157/21/20157/21/2015 12:13:46 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover
GCE15-00108 GCE-Final7/20/20157/21/20157/21/2015 11:39:37 AMAPASS
Mike ###-#### Added new transfer switch to service and established new service and transfer switch. Bonding done at transfer switch, original mains have separation of neutral and grounds. Final ok
GCE15-00108 GCE-Permanent Service7/21/20157/21/20157/21/2015 11:37:39 AMPPASS
Mike ###-#### p/s u/g rec ok
GCE15-00086 GCE-Final7/20/20157/21/20157/21/2015 10:59:18 AMAPASS
Jason ###-#### - requested 1hr. call ahead 3 cooling units installed. Final ok
GCE15-00096 GCE-Final7/20/20157/21/20157/21/2015 10:58:18 AMAPASS
Jason ###-#### - requested 1hr. call ahead Equipment not listed for US, CE listing is now acceptable as per new state law. Final ok
ELE15-02243 Electrical Rough-In7/20/20157/21/20157/21/2015 9:53:12 AMANH
Phone #: ###-#### Inspection requested via web by Celinda Winters No answer at door. Contractor said he would reschedule
ELE15-02223 Electrical Rough-In7/20/20157/21/20157/21/2015 9:08:25 AMAPASS
Inspection requested via web by Rowdy Monroe Rough in ok cover
ELE15-02223 Permanent Service7/21/20157/21/20157/21/2015 9:07:05 AMPPASS
Inspection requested via web by Rowdy Monroe p/s u/g n ok
ELE15-01413 Electrical Rough-In7/20/20157/21/20157/20/2015 3:14:48 PMAPASS
We are requesting a ceiling rough-in for this project.
Our contact is Bud ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate Grid rough in ok cover