Inspections for the day of: Thursday, July 21, 2016.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00451 INSP-Final Inspection7/21/20167/21/20167/21/2016 3:31:43 PMPCANC
Rescheduled for tomorrow at 7:00
BLD16-01252 FIRE-Final Inspection7/21/20167/21/20167/21/2016 3:31:03 PMPFAIL
Provide exit discharge light at the main exit, repair rear exit sign and provide emergency lighting per the plans in the corridor.
BLD16-02454 FIRE-Final Inspection7/21/20167/21/20167/21/2016 3:30:05 PMPFAIL
Repair emergency light upstairs and provide single action hardware at the riser room
BLD16-01182 FIRE-Conference7/20/20167/21/20167/21/2016 3:28:10 PMPDONE
went over life safety requirements
FIR16-00467 INSP-Final Inspection7/20/20167/21/20167/21/2016 3:26:20 PMPCANC
Overbooked. Reschedule for tomorrow morning
FIR16-00427 INSP-Sprinkler Rough-in/Hydro7/21/20167/21/20167/21/2016 3:22:24 PMPCANC
Overbooked. Reschedule for tomorrow morning at 7:30
BLD16-02446 FIRE-Conference7/21/20167/21/20167/21/2016 1:38:08 PMPDONE
Gary, Carl and I went over life safety requirements. Most specifically the need for fire alarm modifications for the new tenant
FIR16-00463 INSP-Final Inspection7/20/20167/21/20167/21/2016 1:36:53 PMPCANC
Moved 1 Head. Rough to cover and Final inspection. Phone #: ###-#### Inspection requested via web by Brett Lawatch
FIR16-00463 INSP-Sprinkler Rough-in7/20/20167/21/20167/21/2016 1:36:22 PMPPASS
Rough to cover passed on the one head in the scope of work but I found another overspaced head outside of the scope of work and per Rick and my conversation I will leave this permit open and let him finish this work prior to a final.
FIR16-00052 INSP-Supply line flush7/20/20167/21/20167/21/2016 10:41:31 AMPFAIL
Arrived on site and found both the underground and overhead pressure guages way under 200psi. I spoke to Gordon and he is going to reschedule. No plans are on site for a rough-in for the draft stops.
FIR16-00052 INSP-Sprinkler Rough-in/Hydro7/20/20167/21/20167/21/2016 10:41:02 AMPFAIL
Arrived on site and found both the underground and overhead pressure guages way under 200psi. I spoke to Gordon and he is going to reschedule. No plans are on site for a rough-in for the draft stops.
BLD16-02663 FIRE-Final Inspection7/20/20167/21/20167/21/2016 10:38:17 AMAPASS
life safety passed
FIR16-00427 INSP-Sprinkler Rough-in7/20/20167/21/20167/21/2016 9:29:50 AMAFAIL
Provide the small documents, heads are located too close to one another, riser is too far from wall, tenting not complete, underground supply is too shallow..ect.
FIR16-00080 INSP-Final Inspection7/14/20167/21/20167/21/2016 9:28:07 AMAPASS
Permit finled. No electrical is functional under the hoods this includes outlets and lighting. If, in the future, these are made functional an electrical shunt may be required.
FIR16-00427 INSP-Sprinkler Rough-in/Hydro7/20/20167/21/20167/21/2016 8:52:39 AMAFAIL
This inspection was for an underground cover. Piping is installed at the other end of the house and is not at the required 4'-6" minimum bury depth. Piping can not be covererd.
FIR16-00455 INSP-Sprinkler Rough-in7/20/20167/21/20167/21/2016 8:46:03 AMAPASS
Todays inspection was just for the underground stub-out to 5'-0". It is ok for cover. We spoke about the CPVC requirment to be with-in 1 1/2" of the wall when exposed.
FIR16-00361 INSP-Final Inspection7/20/20167/21/20167/21/2016 8:25:34 AMAPASS
Permit finaled