Inspections for the day of: Friday, July 21, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02143 Electrical Rough-In7/20/20177/21/20177/21/2017 1:32:43 PMPPASS
please call 20 min before so I can meet inspector at my house. Thank you. Phone #: ###-#### Inspection requested via web by Anthony Bongiovano
Living room, bed and bath ok cover
ELE17-02193 Electrical Rough-In7/21/20177/21/20177/21/2017 1:31:47 PMPPASS
kitchen ceiling grid Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Kitchen suspended ceiling only ok cover
ELE17-02334 Rough-In Permanent Service7/20/20177/21/20177/21/2017 11:03:41 AMAPASS
Late am if you can. Thanks Phone #: ###-#### Inspection requested via web by Dan Rohl
Rough-in ok cover
p/s u/g n ok
ELE17-02293 Final7/18/20177/21/20177/21/2017 10:33:46 AMACANC
ZAK Phone #: ###-####
No final needed just conference
ELE17-02293 Conference7/21/20177/21/20177/21/2017 10:33:37 AMPDONE
ZAK Phone #: ###-####
Discussed wiring of new bath addition, tamper and weather resistant plus GFCI portection of receptacles. Panel change in garage will be done on different day, Dad is helping and is a Cali general contractor seems to have it all handle......
ELE17-01449 Final7/21/20177/21/20177/21/2017 9:51:19 AMAFAIL
Access code 5050+enter Phone #: ###-#### Inspection requested via web by Hidajet Zahic
210.8 All 120v receptacles in a garages shall have GFCI protection
210.8 All GFCI shall be readily accesible
408 Panel screws needed
ELE17-02340 Rough-In Permanent Service7/20/20177/21/20177/21/2017 9:24:45 AMAPASS
Phone #: ###-#### Inspection requested via web by John VanZandt
Rough-in ok cover
p/s u/g n ok