FIR20-00391
| INSP-Sprinkler Rough-in | 7/21/2020 | 7/21/2020 | 7/21/2020 4:06:05 PM | P | PASS |
|
|
Rough to cover inspection for area of work is complete, approved for cover.
Contact Rick Fry For coordination of inspection Phone #: ###-#### Inspection requested via web by Christophe Wilson
|
FIR19-00652
| INSP-Sprinkler Rough-in | 7/21/2020 | 7/21/2020 | 7/21/2020 4:04:44 PM | P | PART |
|
|
Partial rough to cover inspection for garage sprinkler piping complete. Piping can be painted before rough in inspection requests.
Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
|
BLD19-04313
| FIRE-Final Inspection | 7/21/2020 | 7/21/2020 | 7/21/2020 1:02:46 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for areas of work complete, signatures provided on permit sign off card.
screened // Chet Phone #: ###-####
|
FIR19-00702
| INSP-Final Inspection | 7/20/2020 | 7/21/2020 | 7/21/2020 1:01:11 PM | P | FAIL |
|
|
PIV tamper not installed/wired. Hydrostatic test for overhead fire sprinkler has not been completyed/documented under permit notes. Need fire alarm inspection scheduled to coincide with fire sprinkler final for sprinkler monitoring.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00185
| INSP-Final Inspection | 7/19/2020 | 7/21/2020 | 7/21/2020 10:19:36 AM | A | PASS |
|
|
Final fire alarm inspection for scope of work is complete.
Please Call Jim before Inspection. Phone #: ###-#### Inspection requested via web by Jim Shilton
|
FIR19-00940
| INSP-Supply line flush | 7/20/2020 | 7/21/2020 | 7/21/2020 9:15:13 AM | A | DONE |
|
|
Main line flush complete to include remote FDC piping.
Call James if anything comes up, scheduled for 9am with Stacy/SUEZ and Jim Page. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|