Inspections for the day of: Wednesday, July 22, 1998.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE98-02416 INSP - Electrical Rough-In7/21/19987/22/19987/22/1998 12:00:00 AMAPASS
SERVICE MIKE ###-#### REQUESETED CONFERENCE ONLY.
ELE98-02436 INSP - Electrical Rough-In7/21/19987/22/19987/22/1998 12:00:00 AMAFAIL
07/22/98 403 - NEED A WALL AND CEILING COVER ###-#### CHUCK NEC: 210-52 (D). BATHROOM G.F.C.I. RECEP. SHALL BE 20 AMP; NO OTHER OUT
ELE98-02477 INSP - Electrical Rough-In7/21/19987/22/19987/22/1998 12:00:00 AMAPASS
MOVING SERVICE MIKE ###-####
ELE98-02484 INSP - Electrical Rough-In7/21/19987/22/19987/22/1998 12:00:00 AMAFAIL
TERRY ###-#### NEC: 517-3. 517-13. PATIENT CARE, GROUNDING.
ELE98-01164 INSP - Electrical Rough-In7/21/19987/22/19987/22/1998 12:00:00 AMAPART
07/22/98 403 - Scheduled by Hello!. P.V.C. CONDUIT INSTALLED ON 5TH FLOOR DECKING.
ELE98-02002 INSP - Electrical Rough-In7/22/19987/22/19987/22/1998 12:00:00 AMPPART
07/22/98 403 - r/i jim ###-#### CEILING RECESSED INCANDESCENT FIXTURE R/I.
ELE98-02492 INSP - Final7/22/19987/22/19987/22/1998 12:00:00 AMPNR
07/22/98 403 - rick ###-####..trans jms.. CONTRACTOR WILL RESCHEDULE.
ELE98-02496 INSP - Electrical Rough-In7/22/19987/22/19987/22/1998 12:00:00 AMPFAIL
rick ###-#### remodel of three rooms and service NEC: 250-81(C). CONCRETE INCASED GROUNDING ELECTRODE REQUIRED. NEC: 373-5. CABLES SHALL BE SECURED TO PANELBOARD, CABINET, ETC. BCEC: IN HOUSE FAN SHALL HAVE MANUAL SWITCH AND TIMER. NEC: 336-18.CABLES SHALL BE SUPPORTED EVERY 4 1/2 FEET.