ELE98-02416
| INSP - Electrical Rough-In | 7/21/1998 | 7/22/1998 | 7/22/1998 12:00:00 AM | A | PASS |
|
|
SERVICE MIKE ###-#### REQUESETED CONFERENCE ONLY.
|
ELE98-02436
| INSP - Electrical Rough-In | 7/21/1998 | 7/22/1998 | 7/22/1998 12:00:00 AM | A | FAIL |
|
|
07/22/98 403 - NEED A WALL AND CEILING COVER ###-#### CHUCK NEC: 210-52 (D). BATHROOM G.F.C.I. RECEP. SHALL BE 20 AMP; NO OTHER OUT
|
ELE98-02477
| INSP - Electrical Rough-In | 7/21/1998 | 7/22/1998 | 7/22/1998 12:00:00 AM | A | PASS |
|
|
MOVING SERVICE MIKE ###-####
|
ELE98-02484
| INSP - Electrical Rough-In | 7/21/1998 | 7/22/1998 | 7/22/1998 12:00:00 AM | A | FAIL |
|
|
TERRY ###-#### NEC: 517-3. 517-13. PATIENT CARE, GROUNDING.
|
ELE98-01164
| INSP - Electrical Rough-In | 7/21/1998 | 7/22/1998 | 7/22/1998 12:00:00 AM | A | PART |
|
|
07/22/98 403 - Scheduled by Hello!. P.V.C. CONDUIT INSTALLED ON 5TH FLOOR DECKING.
|
ELE98-02002
| INSP - Electrical Rough-In | 7/22/1998 | 7/22/1998 | 7/22/1998 12:00:00 AM | P | PART |
|
|
07/22/98 403 - r/i jim ###-#### CEILING RECESSED INCANDESCENT FIXTURE R/I.
|
ELE98-02492
| INSP - Final | 7/22/1998 | 7/22/1998 | 7/22/1998 12:00:00 AM | P | NR |
|
|
07/22/98 403 - rick ###-####..trans jms.. CONTRACTOR WILL RESCHEDULE.
|
ELE98-02496
| INSP - Electrical Rough-In | 7/22/1998 | 7/22/1998 | 7/22/1998 12:00:00 AM | P | FAIL |
|
|
rick ###-#### remodel of three rooms and service NEC: 250-81(C). CONCRETE INCASED GROUNDING ELECTRODE REQUIRED. NEC: 373-5. CABLES SHALL BE SECURED TO PANELBOARD, CABINET, ETC. BCEC: IN HOUSE FAN SHALL HAVE MANUAL SWITCH AND TIMER. NEC: 336-18.CABLES SHALL BE SUPPORTED EVERY 4 1/2 FEET.
|