Inspections for the day of: Thursday, July 22, 2004.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00189 INSP-Final Inspection7/15/20047/22/20047/22/2004 12:00:00 AMAFAIL
bryan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Panel in trouble from NAC panel; smoke detectors overspaced - see plans; need lockout on NAC panel breaker; remove local alarm signs at manual pulls 7/22/2004 10:51:19 AM
BLD03-00062 FIRE-Final Inspection7/21/20047/22/20047/22/2004 12:00:00 AMAPASS
BLD03-01845 FIRE-Conference7/15/20047/22/20047/22/2004 12:00:00 AMPPART
To check on alarm plans Talked to Phil Omas and he said he sent an estimate to Van Auker for the installation of the new FACP; will check status again next week 7/22/2004 1:30:19 PM
FIR04-00167 INSP-Sprinkler Rough-in/Hydro7/21/20047/22/20047/22/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 7/21/2004 at 2:09:23 PM. Contact: ###-####. NW operating room okay to cover 7/22/2004 4:39:07 PM