Inspections for the day of: Thursday, July 22, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-03033 FIRE-Final Inspection7/21/20047/22/20047/22/2004 12:00:00 AMAFAIL
Provide lever hardware per approved plans on all doors. Remove thumbturn from main entry/exit. Provide sticker as discussed on the main entry/exit. Provide verification the HVAC units are under 2000cfm. 7/22/2004 10:02:14 AM
BLD04-01019 FIRE-Final Inspection7/21/20047/22/20047/22/2004 12:00:00 AMAPASS
Life safety finaled 7/22/2004 8:33:19 AM
FIR04-00378 INSP-Final Inspection7/22/20047/22/20047/22/2004 12:00:00 AMAPASS
Fire sprinklers finaled
FIR04-00370 INSP-Sprinkler Rough-in/Hydro7/22/20047/22/20047/22/2004 12:00:00 AMPPASS
Sprinkler rough-in OK. Need new hydraulic sticker, spare heads and tape off of sprinkler uprights to final. 7/22/2004 3:46:36 PM
FIR03-00779 INSP-Sprinkler Rough-in/Hydro7/22/20047/22/20047/22/2004 12:00:00 AMPPART
Forward flush of the backflow preventer and the additional head in the closet are ok. Still need alarm connections and hanger from previous correction notice to be done. 7/22/2004 1:58:54 PM
FIR04-00370 INSP-Sprinkler Rough-in/Hydro7/22/20047/22/20047/22/2004 12:00:00 AMPPART
Hydro test OK. 7/22/2004 11:18:46 AM
FIR04-00407 INSP-Conference7/22/20047/22/20047/22/2004 12:00:00 AMPDONE
Met with tim, superintendant, and a representative from the mechanical and fire alarm contractors. We discussed the removal of a duct smoke detector that was not needed in the Training room. The hvac unit is 1800cfm and serves only that room. I agreed with the removal 7/22/2004 3:48:31 PM