Inspections for the day of: Friday, July 22, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00262 INSP-Final Inspection7/21/20057/22/20057/22/2005 3:48:23 PMAPART
Final pending relocation of wall mounted strobe fire alarm notification devices to within code required heights AFF.
BLD04-02153 FIRE-Final Inspection7/21/20057/22/20057/22/2005 3:27:05 PMAPART
Final pending approval of foreward flow test for backflow preventer at fire supply, and relocation of strobe FA notification devices to meet code required heights AFF.
BLD05-00463 FIRE-Final Inspection7/22/20057/22/20057/22/2005 3:25:02 PMPPART
Final pending sign-off of fire alarm and fire sprinkler permits, all other life safety issues are satisfactory.
FIR05-00308 INSP-Final Inspection7/21/20057/22/20057/22/2005 3:21:32 PMAPART
Final pending relocation of wall mounted strobe fire alarm notification devices to within code required heights AFF.
FIR05-00372 INSP-Sprinkler Rough-in7/21/20057/22/20057/22/2005 2:53:07 PMPCANC
matt; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Inspection cancelled from web by: Alicia Pauley
BLD04-02988 FIRE-Final Inspection7/21/20057/22/20057/22/2005 2:20:30 PMAFAIL
Related fire sprinkler and fire alarm permits must be scheduled, inspected, and approved prior to BLD life safety sign-off. Defficient life safety items include but are not limited to; repair non-functional emergency lights and exit signs, verify functionality of duct smoke detectors, provide building address, provide approved hardware at custodial room.
FIR05-00386 INSP-Final Inspection7/22/20057/22/20057/22/2005 2:13:01 PMPFAIL
A sprinkler head is not installed or shown on plans in a closet at the NE corner, missing hanger at arm over in office north side, heads in several offices on the west side are overspaced from adjacent walls, no further items inspected at this time. Contractor to re-schedule inspection when ready.
BLD05-00463 FIRE-Final Inspection7/21/20057/22/20057/22/2005 11:33:59 AMAFAIL
Provide approved hardware at pocket door to office 102, provide door closer and seal at medical gas storage closet as instructed on review notes, provide suite or space identification.
BLD04-02153 FIRE-Alarm Testing7/21/20057/22/20057/22/2005 11:30:12 AMACANC
Duplicate inspection.
BLD05-00463 FIRE-Alarm Testing7/21/20057/22/20057/22/2005 11:29:29 AMACANC
Duplicate inspection.
FIR05-00111 INSP-Final Inspection7/21/20057/22/20057/22/2005 11:14:01 AMAFAIL
Foreward flow test failed to produce required gpm.