Inspections for the day of: Friday, July 22, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00063 FIR-Aging Inspection7/22/20057/22/20057/25/2005 10:56:09 AM NR
I spoke to the general contractor sid; Phone #: ###-####, he stated that more sprinkler work is needed and once that is done the inspection would be called in
FIR05-00424 INSP-Supply line flush7/22/20057/22/20057/22/2005 3:34:14 PMPPART
Inspection was for cover. Underground piping is ok to cover
FIR04-00737 INSP-Sprinkler Rough-in7/20/20057/22/20057/22/2005 3:31:32 PMPCANC
Contact Dave Around 1 PM please.; Phone #: ###-#### Cancelled per Dave's request.
FIR05-00043 INSP-Sprinkler Rough-in/Hydro7/22/20057/22/20057/22/2005 2:39:06 PMPPASS
Permit finaled
FIR05-00227 INSP-Final Inspection7/22/20057/22/20057/22/2005 2:38:45 PMPPASS
Permit finaled
BLD05-00747 FIRE-Final Inspection7/22/20057/22/20057/22/2005 11:53:08 AMPPASS
Life safety finaled
FIR05-00346 INSP-Sprinkler Rough-in/Hydro7/22/20057/22/20057/22/2005 11:52:42 AMAPART
Sprinkler piping on second floor can be covered. Sprinkler piping on first floor can be covered except for the west side north end office area. Due to upright sprinklers being blocked by duct work additional uprights will be required. Resubmit plans with showing this new work.
BLD02-01235 FIRE-Final Inspection7/21/20057/22/20057/22/2005 11:50:42 AMAFAIL
Repair the three exit signs as marked on plans, provide one additional emergency light as marked on plans. Provide duct smoke detectors as shown on sheet M1. Remote annunciators may be required if inaccessible or over 10' above finish floor.
FIR04-00128 FIR-Aging Inspection7/22/20057/22/20057/22/2005 9:07:25 AM PASS
permit finaled
FIR04-00121 FIR-Aging Inspection7/22/20057/22/20057/22/2005 9:03:53 AM PASS
Permit finaled