BLD07-02689
| FIRE-Final Inspection | 7/21/2008 | 7/22/2008 | 7/23/2008 5:49:39 PM | A | PART |
|
|
Pending approved hardware at the office slider doors.
|
BLD08-00197
| FIRE-Final Inspection | 7/21/2008 | 7/22/2008 | 7/23/2008 5:48:15 PM | A | PASS |
|
|
Noted corrections are complete, fire life safety passed.
|
FIR08-00485
| INSP-Final Inspection | 7/21/2008 | 7/22/2008 | 7/23/2008 5:47:37 PM | A | PASS |
|
|
Fire sprinkler modifications are acceptable, permit finaled.
|
FIR07-00606
| INSP-Sprinkler Rough-in | 7/21/2008 | 7/22/2008 | 7/22/2008 4:15:06 PM | P | FAIL |
|
|
Reinspection completed for Areas E,F,I and J failed due to several deficient items including 3 missing hangers, 4 missing upright heads at two mechanical rooms, overspaced pendent heads at two locations in the common corridor, overspaced heads at one classroom, missing all seismic bracing at the upper mechanical room, overspaced classroom vestibule x2, min. spacing is exceeded at a science room, light fixture obstruction at a storage room, one overspaced head off an adjacent wall in classroom J10, need to verify correct temp. heads at the room marked "kiln room". Concluded inspection until repairs are made and project is ready for field review.
|
FIR06-00595
| INSP-Final Inspection | 7/21/2008 | 7/22/2008 | 7/22/2008 4:01:06 PM | A | PART |
|
|
Final pending fire hat at elevators, per contractor the supervisory tamper switch at the 5th floor NE riser has been repaired and correctly programed-will verify at final inspection in conjunction with elevator controls as discussed.
|
FIR08-00289
| INSP-Sprinkler Rough-in | 7/22/2008 | 7/22/2008 | 7/22/2008 1:29:27 PM | P | PART |
|
|
Site visit to verify seismic restraint at beam clamps for system piping hangers prior to structural fireproofing throughout.
|
FIR08-00210
| INSP-Sprinkler Rough-in/Hydro | 7/21/2008 | 7/22/2008 | 7/22/2008 12:58:55 PM | P | PART |
|
|
OH hydrostatic retest passed.
|
MIS08-00110
| FIR-Conference | 7/22/2008 | 7/22/2008 | 7/22/2008 12:40:20 PM | P | DONE |
|
|
Work does not appear pertaining to fire alarm, fire sprinkler or fire life safety review.
|
BLD08-01322
| FIRE-Final Inspection | 7/22/2008 | 7/22/2008 | 7/22/2008 12:09:43 PM | P | FAIL |
|
|
Need to provide a current annual certification for the posted fire extinguisher, remainder of life safety is acceptable.
|
FIR08-00452
| INSP-Sprinkler Rough-in | 7/21/2008 | 7/22/2008 | 7/22/2008 10:51:13 AM | A | FAIL |
|
|
Field installation does not match approved plans including layout at the east side rooms, added head due to ceiling height change at the west side, contractor has installed 3/4 pendent heads despite approved drawings indicating 1/2 to be used, also lacking coverage for exposed combustible construction above the drop ceiling, corner adjacent to the south exit door is unprotected, provide accurate drawings prior to next inspection, ceiling cover is not approved at this time.
|
BLD08-01556
| FIRE-Final Inspection | 7/21/2008 | 7/22/2008 | 7/22/2008 10:15:27 AM | A | PASS |
|
|
Life safety inspection completed acceptable, inspection passed.
|
BLD06-02930
| FIRE-Final Inspection | 7/21/2008 | 7/22/2008 | 7/21/2008 8:00:42 AM | A | CANC |
|
|
Life Safety final Phone #: ###-#### Internet Inspection Request from: Wayne Berry Inspection cancelled from web by: Wayne Berry
|