Inspections for the day of: Wednesday, July 22, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00033 INSP-Sprinkler Rough-in/Hydro7/22/20097/22/20097/22/2009 4:52:49 PMPPART
OH hydrostatic testing for systems #28, 28 rack, 29, 29 rack, 27, 28 and riser room 5 passed.
FIR09-00033 INSP-Sprinkler Rough-in/Hydro7/16/20097/22/20097/22/2009 4:51:25 PMAPART
Rough-in inspection completed for OH system #26, noted items include beam obstructions as previously noted, one sprig-up spaced incorrectly, main change at a different location than what is shown on stamped plans, EQ bracing shown but not installed.
BLD08-01139 FIRE-Final Inspection7/21/20097/22/20097/22/2009 4:46:59 PMANR
Need project related fire alarm permit issued, requested for inspection and finaled prior to BLD final.
BLD08-01138 FIRE-Final Inspection7/21/20097/22/20097/22/2009 4:46:41 PMANR
Need project related fire alarm permit issued, requested for inspection and finaled prior to BLD final.
BLD08-01134 FIRE-Final Inspection7/21/20097/22/20097/22/2009 4:46:25 PMANR
Need project related fire alarm permit issued, requested for inspection and finaled prior to BLD final.
BLD08-01141 FIRE-Final Inspection7/21/20097/22/20097/22/2009 4:46:05 PMANR
Need project related fire alarm permit issued, requested for inspection and finaled prior to BLD final.
FIR09-00164 INSP-Sprinkler Rough-in/Hydro7/21/20097/22/20097/22/2009 4:44:20 PMAPART
Overhead rough-in for the first floor classroom wing sheet FP-2 okayed as red lined with today's date. Sizing changes at the main to match with approved plan set.
FIR09-00370 INSP-Sprinkler Rough-in7/21/20097/22/20097/22/2009 4:40:49 PMPPART
Noted corrections verified for completion, overhead modifications okay for cover.