FIR11-00159
| INSP-Sprinkler Rough-in | 7/21/2011 | 7/22/2011 | 7/22/2011 2:54:29 PM | P | PASS |
|
|
Request to rough-to-cover inspection for several areas is approved. See the city approved "plan modification" for areas marked "ok". I let Joe know that the maximum spacing for the lateral bracing on the lower level is 30' and 80' for the longitudinals and to refer to nfpa 13 table 9.3.5.3.2 (a)
|
BLD11-00926
| FIRE-Final Inspection | 7/21/2011 | 7/22/2011 | 7/22/2011 2:52:13 PM | A | PASS |
|
|
Life safety passed
|
FIR11-00338
| INSP-Final Inspection | 7/21/2011 | 7/22/2011 | 7/22/2011 2:51:43 PM | A | PASS |
|
|
Permit finaled
|
FIR11-00259
| INSP-Final Inspection | 7/20/2011 | 7/22/2011 | 7/22/2011 11:40:34 AM | A | PASS |
|
|
Permit finaled
|
FIR11-00303
| INSP-Final Inspection | 7/21/2011 | 7/22/2011 | 7/22/2011 11:39:57 AM | A | PASS |
|
|
Permit finaled
|