Inspections for the day of: Friday, July 22, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00159 INSP-Sprinkler Rough-in7/21/20117/22/20117/22/2011 2:54:29 PMPPASS
Request to rough-to-cover inspection for several areas is approved. See the city approved "plan modification" for areas marked "ok". I let Joe know that the maximum spacing for the lateral bracing on the lower level is 30' and 80' for the longitudinals and to refer to nfpa 13 table 9.3.5.3.2 (a)
BLD11-00926 FIRE-Final Inspection7/21/20117/22/20117/22/2011 2:52:13 PMAPASS
Life safety passed
FIR11-00338 INSP-Final Inspection7/21/20117/22/20117/22/2011 2:51:43 PMAPASS
Permit finaled
FIR11-00259 INSP-Final Inspection7/20/20117/22/20117/22/2011 11:40:34 AMAPASS
Permit finaled
FIR11-00303 INSP-Final Inspection7/21/20117/22/20117/22/2011 11:39:57 AMAPASS
Permit finaled