Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-01677 FIRE-Conference7/12/20137/22/20137/24/2013 3:45:25 PMAPASS
Susan has removed the old lights.
FIR13-00147 INSP-Final Inspection7/22/20137/22/20137/22/2013 4:11:26 PMPPASS
Permit finaled
BLD13-01802 FIRE-Final Inspection7/22/20137/22/20137/22/2013 3:53:31 PMPPASS
Life safety passed. Owner to remove the thumbturn deadbolt from the main exit and install keyed as per the approved drawings prior to the building inspection.. I let the owner know that the building inspector may require lever hardware on the restroom door based on a plan review note from a previous tenant remodel.
FIR12-00695 INSP-Sprinkler Rough-in7/22/20137/22/20137/22/2013 3:50:39 PMPCANC
Cancelled due to being over booked. Rescheduled for tomorrow.
FIR12-00551 INSP-Final Inspection7/18/20137/22/20137/22/2013 3:45:20 PMAPASS
permit finaled
BLD13-01431 FIRE-Final Inspection7/22/20137/22/20137/22/2013 2:47:06 PMPPASS
Life safety passed. Contractor chose to install passage hardware on the access door to the island restrooms.
BLD13-01913 FIRE-Final Inspection7/22/20137/22/20137/22/2013 2:40:18 PMPFAIL
Shay and I spoke with Carl Madson and determined that an updated floor plan needs to be submitted that shows the island restroom, small enclosed corridor and the separate business in suite 102. The fire extinguisher has been inspected.
FIR13-00115 INSP-Sprinkler Rough-in7/22/20137/22/20137/22/2013 2:13:45 PMPPASS
See the city approved plans for additional rooms marked "ok" in red where the sprinkler piping is ok to cover.
FIR13-00292 INSP-Final Inspection7/17/20137/22/20137/22/2013 2:04:51 PMPPASS
Permit finaled. Netcon was a 5
FIR13-00148 INSP-Final Inspection7/22/20137/22/20137/22/2013 1:49:04 PMPCANC
Would like to perform this inspection in conjunction with alarm testing. Please call Brad Bettencourt at the office if there are any issues or questions. Phone #: ###-#### >> Inspection requested via web by Jeff Packham Inspection cancelled from web by: Brad Bettencourt
FIR13-00095 INSP-Sprinkler Rough-in/Hydro7/19/20137/22/20137/22/2013 10:25:34 AMAPASS
Overhead hydro test passed. I noted that the fire dept connection has not been installed on the street side of the building. I spoke with Don and he is going to contact Tim Frost to verify an approved location for the fdc and the electric alarm bell.
FIR13-00095 INSP-Supply line flush7/19/20137/22/20137/22/2013 10:23:30 AMACANC
Cancel per Don Phone #: ###-####
BLD13-01657 FIRE-Final Inspection7/19/20137/22/20137/22/2013 10:03:57 AMAFAIL
Repair the rear exit sign and remove the thumbturn lock or remove the exit sign (not required) and the lock can remain since the space only requires one exit. Also sprinkler coverage is missing in the rear/east room. This work will require a separate permit.
BLD13-00821 FIRE-Conference7/18/20137/22/20137/22/2013 10:00:48 AMPDONE
Forest, the info you had requested is as follows: TVFP did the cetification, system 525 lbs. last date inspected 8-08-2008 Phone #: ###-#### >> Inspection requested via web by phil doble
BLD13-00882 FIRE-Final Inspection7/19/20137/22/20137/22/2013 9:25:58 AMAFAIL
Provide approved door hardware on doors as marked in red on plan sheet A3.1
FIR13-00255 INSP-Final Inspection7/18/20137/22/20137/22/2013 8:33:07 AMAPART
Dish washing area as marked on the city approved plans is ok for cover.
FIR13-00249 INSP-Sprinkler Rough-in7/19/20137/22/20137/22/2013 7:04:39 AMAPASS
Underground piping is approved to cover as marked on the city approved plans.
FIR13-00250 INSP-Sprinkler Rough-in7/19/20137/22/20137/22/2013 7:04:13 AMAPASS
Underground piping is approved to cover as marked on the city approved plans.