FIR14-00460
| INSP-Sprinkler Rough-in | 7/22/2014 | 7/22/2014 | 7/23/2014 2:49:31 PM | P | PART |
|
|
Okay to cover UG fire supply line
|
BLD14-01232
| FIRE-Final Inspection | 7/22/2014 | 7/22/2014 | 7/22/2014 3:01:12 PM | P | PASS |
|
|
Life safety passed provided door hardware, including signage, per plan review annotations at the main entry/exit is revised prior to structural final inspection.
|
FIR14-00269
| INSP-Sprinkler Rough-in | 7/22/2014 | 7/22/2014 | 7/22/2014 2:58:02 PM | P | PART |
|
|
Inspection for cover at grid ceilings completed to date- Items noted include; insufficient coverage the janitors and IT rooms due to OTS ceiling configuration, need to add upright coverage at a concealed space overbuild above classroom 119. Commons classroom, corridor grid, and main tie-in above the 5th grade classroom are not yet finished. Verified added uprights along the north and south main corridor rated walls. Discussed hydrostatic testing per review notes and NFPA guidelines. Need record drawings for field modifications. Remainder of classrooms approved for ceiling cover as noted on plans.
|
BLD13-01344
| FIRE-Final Inspection | 7/21/2014 | 7/22/2014 | 7/22/2014 1:36:24 PM | P | FAIL |
|
|
Correction items include; post building address numbers, install exit signs per plan sheet AS 101, provide fire extinguisher, door hardware at the restrooms needs to meet egress requirements per IBC.
|
FIR14-00368
| INSP-Final Inspection | 7/21/2014 | 7/22/2014 | 7/22/2014 11:59:06 AM | A | PART |
|
|
Pharmacy area remodel and coffee shop kiosk both passed final walkthrough. Final pending one demo head per plans. Noted existing fire sprinkler system appears overdue annual certification and inspection.
|
BLD13-03418
| FIRE-Final Inspection | 7/21/2014 | 7/22/2014 | 7/22/2014 10:07:49 AM | A | PART |
|
|
Regarding completion of work at the basement level.
|
FIR14-00327
| INSP-Sprinkler Rough-in | 7/21/2014 | 7/22/2014 | 7/22/2014 10:06:43 AM | A | PART |
|
|
Okay to cover overhead work at the corridor grid ceiling areas.
|