Inspections for the day of: Wednesday, July 22, 2015.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00842 ELE-Aging Inspection7/22/20157/22/20157/24/2015 1:34:44 PM DONE
Called contractor, he said job was cancelled. He is going to check and see if refundable since no inspection have been performed.
ELE13-01338 Final7/22/20157/22/20157/22/2015 2:48:57 PMPPASS
Disconnecting means confirmed. Final ok
ELE13-00804 ELE-Aging Inspection7/22/20157/22/20157/22/2015 2:47:58 PM DONE
Still under construction
ELE13-00810 ELE-Aging Inspection7/22/20157/22/20157/22/2015 2:47:24 PM DONE
Drove by and inspected
ELE13-00810 Final7/22/20157/22/20157/22/2015 2:46:56 PMPPASS
Disconnect and listing confirmed. Final ok
ELE15-02170 Final7/22/20157/22/20157/22/2015 2:42:28 PMPPASS
The issue with the parallel path has been corrected. Phone #: ###-#### Inspection requested via web by Dave Koeppen Generator to be set in future. Final ok
ELE15-02240 Permanent Service7/22/20157/22/20157/22/2015 2:31:02 PMPCANC
Phone #: ###-#### Inspection requested via web by Randy Fletcher Needed Final
ELE15-02240 Final7/22/20157/22/20157/22/2015 2:02:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Fletcher Final ok
ELE15-01280 Final7/22/20157/22/20157/22/2015 1:46:59 PMPPASS
Swimming pool electrical Phone #: ###-#### Inspection requested via web by Lars Johnson Pool Final ok
ELE15-02028 Final7/21/20157/22/20157/22/2015 1:25:51 PMACANC
Jim Phone #: ###-#### Needed P/S inspection
ELE15-02028 Permanent Service7/22/20157/22/20157/22/2015 1:23:57 PMPFAIL
Jim Phone #: ###-#### 110.26(C)(3)- Work space ok however when door is open on gear it blocks egress from work space. Unobstructed egress required.
ELE15-02263 Temporary Service7/22/20157/22/20157/22/2015 12:32:07 PMPPASS
READY NOW Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE15-00768 Final7/21/20157/22/20157/22/2015 11:13:04 AMAPASS
Code for house 7105 in case no one is there. Call Lloyd ###-#### for any questions Phone #: ###-#### Inspection requested via web by Jerry Moore Final ok
ELE15-02175 Electrical Rough-In7/22/20157/22/20157/22/2015 10:41:38 AMAPASS
pole bases ; underground Phone #: ###-#### Inspection requested via web by Lee VanSchoiack 4 remaining pole bases and underground rough in ok cover
ELE15-01695 Final7/21/20157/22/20157/22/2015 10:17:01 AMAFAIL
The access code is 6949, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren 314.25- All boxes shall have covers. Kitchen
ELE15-02153 Permanent Service7/22/20157/22/20157/22/2015 9:49:04 AMPPASS
p/s u/g n ok
ELE15-02243 Electrical Rough-In7/21/20157/22/20157/22/2015 9:16:16 AMAPASS
Contractor will be there Phone #: ###-#### Inspection requested via web by Celinda Winters New switches, circuit for floor heat, vanity outlet rough in ok cover
ELE15-02165 Electrical Rough-In7/21/20157/22/20157/22/2015 9:06:51 AMAPASS
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton Outer walls to be fished or surface mounted. Interior wall rough in ok cover
ELE15-01928 Electrical Rough-In7/20/20157/22/20157/21/2015 2:42:04 PMPCANC
Matt Brown is on site 7:00am to 3:00pm Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell