FIR14-00603
| INSP-Sprinkler Rough-in/Hydro | 7/22/2015 | 7/22/2015 | 7/22/2015 2:51:09 PM | P | PASS |
|
|
Hydrostatic test passed/complete on both dry systems covering parking garage, 1st level,
|
FIR14-00815
| INSP-Sprinkler Rough-in/Hydro | 7/22/2015 | 7/22/2015 | 7/22/2015 2:48:30 PM | P | PART |
|
|
Hydrostatic test passed/complete on wet systems supplying 2nd, 3rd and 4th floors, total of 6 wet systems tested, club house wet system still needs hydrostatically tested.
|
FIR15-00454
| INSP-Alarm Testing | 7/20/2015 | 7/22/2015 | 7/22/2015 1:33:27 PM | P | PART |
|
|
Alarm testing complete, will not final until an updated as-build drawing is provided, numerous active devices in tenant space but not on the city approved drawings.
|
FIR15-00096
| INSP-Sprinkler Rough-in | 7/21/2015 | 7/22/2015 | 7/22/2015 11:25:26 AM | A | PART |
|
|
Inspected drop down ceiling area's in rooms 501, 502, 503, 506, 514, 515, 522, 534, 535, 536, 537, 540, 541, 542, 543, approved for cover
|
BLD15-00361
| FIRE-Final Inspection | 7/22/2015 | 7/22/2015 | 7/22/2015 10:21:58 AM | A | PASS |
|
|
Life fire safety passed/complete
|
FIR15-00469
| INSP-Sprinkler Rough-in/Hydro | 7/21/2015 | 7/22/2015 | 7/22/2015 8:48:37 AM | A | PART |
|
|
Notated area's approved for cover with red ink on the city approved drawings.
|
FIR14-00603
| INSP-Sprinkler Rough-in/Hydro | 7/21/2015 | 7/22/2015 | 7/22/2015 8:41:15 AM | A | CANC |
|
|
This is a hydro request for the dry system. Mark is the contact. Thanks. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|