BLD15-04346
| FIRE-Final Inspection | 7/21/2016 | 7/22/2016 | 7/22/2016 3:44:55 PM | A | PART |
|
|
A temporary occupancy is approved for 30 days with Scott's permission. For a final I need the project related fire alarm permit finaled which includes re-submittals and a map, and I need the building plan modifications for the revised fire pump room to be approved and any corrections implemented.
|
FIR16-00122
| INSP-Final Inspection | 7/22/2016 | 7/22/2016 | 7/22/2016 3:44:08 PM | A | PART |
|
|
A temporary occupancy is approved for 30 days with Scott's permission. For a final I need the fire alarm resubmittals approved a map and NFPA 72's.
|
FIR16-00052
| INSP-Sprinkler Rough-in/Hydro | 7/21/2016 | 7/22/2016 | 7/22/2016 2:37:36 PM | P | PART |
|
|
For a cover inspection to be approved I need all of the draft stops installed per plan (one is missing entirely). Insulation in several locations is hanging down and blocking upright sprinkler head coverage. As per a previous request I need approved plans showing the extended coverage sidewalls in the northwest rooms. The overhead hydro test passed but the underground hydro test failed.
|
FIR16-00052
| INSP-Supply line flush | 7/21/2016 | 7/22/2016 | 7/22/2016 2:18:19 PM | P | FAIL |
|
|
The underground hydro test failed so no flush was performed.
|
BLD15-03897
| FIRE-Final Inspection | 7/22/2016 | 7/22/2016 | 7/22/2016 1:46:20 PM | P | PASS |
|
|
Life safety passed. Per Boise Fire Dept. a man gate will not be required at the new hanger building allowing access to the flight line due to additional fire hydrants near the flight line and vehicle access from a neigboring street and gate.
|
BLD16-01915
| FIRE-Final Inspection | 7/22/2016 | 7/22/2016 | 7/22/2016 1:36:56 PM | P | PASS |
|
|
life safety passed
|
FIR16-00359
| INSP-Final Inspection | 7/20/2016 | 7/22/2016 | 7/22/2016 1:16:49 PM | A | PASS |
|
|
permit finaled
|
BLD16-02454
| FIRE-Final Inspection | 7/21/2016 | 7/22/2016 | 7/22/2016 10:24:02 AM | A | PASS |
|
|
Life safety passed
|
BLD16-01280
| FIRE-Final Inspection | 7/22/2016 | 7/22/2016 | 7/22/2016 8:26:20 AM | P | PASS |
|
|
life safety passed
|
FIR16-00451
| INSP-Final Inspection | 7/21/2016 | 7/22/2016 | 7/22/2016 8:25:22 AM | A | PASS |
|
|
Permit finaled
|
BLD16-01915
| FIRE-Final Inspection | 7/21/2016 | 7/22/2016 | 7/22/2016 8:23:45 AM | A | CANC |
|
|
Not ready for final life safety due to missing ceiling tile. I did test the emergency lights and exit signs which tested ok.
|
FIR16-00467
| INSP-Final Inspection | 7/21/2016 | 7/22/2016 | 7/22/2016 8:19:17 AM | A | PASS |
|
|
permit finaled
|
FIR16-00427
| INSP-Sprinkler Rough-in/Hydro | 7/21/2016 | 7/22/2016 | 7/22/2016 8:16:45 AM | A | PASS |
|
|
Rough-in and tenting passed. Leroy was going to modify tenting at the west end of the house. Piping can be covered. Underground is still not deep enough and the supply piping under the house still needs verified.
|
FIR16-00359
| INSP-Sprinkler Rough-in | 7/20/2016 | 7/22/2016 | 7/22/2016 8:14:51 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
|