FIR07-00273
| FIR-Aging Inspection | 7/22/2016 | 7/22/2016 | 7/22/2016 2:50:52 PM | | CANC |
|
|
|
FIR16-00363
| INSP-Alarm Testing | 7/22/2016 | 7/22/2016 | 7/22/2016 1:58:12 PM | P | CANC |
|
|
Inspection request cancelled, no point of contact information was given for this project, contacted Protex Office, phone number ###-####, phone call went to voicemail, left a message stating that if a point of contact is not provided then inspection request will need to be rescheduled.
|
BLD15-01107
| FIRE-Final Inspection | 7/21/2016 | 7/22/2016 | 7/22/2016 1:54:27 PM | P | CANC |
|
|
Inspection request cancelled per conversation with point of contact, Ed Phone #: ###-####. Fire alarm contractor has to make changes to the audio visual devices located in the bathrooms with the showers, when modifications are completed a final fire alarm inspection will be called in to coincide with the final life fire safety inspection.
|
FIR15-00861
| INSP-Sprinkler Rough-in/Hydro | 7/22/2016 | 7/22/2016 | 7/22/2016 1:31:59 PM | P | PASS |
|
|
Rough to cover inspection complete for level 7, hydrostatic test complete for overhead fire sprinkler piping on level 7, tamper switch and flow switch satisfactorily tested for level 7.
|
FIR15-00831
| INSP-Sprinkler Rough-in/Hydro | 7/21/2016 | 7/22/2016 | 7/22/2016 1:28:41 PM | A | PASS |
|
|
Rough to cover inspection complete for level 6, hydrostatic test complete for overhead fire sprinkler piping on level 6, tamper switch and flow switch satisfactorily tested for level 6.
|
FIR16-00010
| INSP-Sprinkler Rough-in/Hydro | 7/21/2016 | 7/22/2016 | 7/22/2016 1:27:36 PM | A | PASS |
|
|
Rough to cover inspection complete for level 8, hydrostatic test complete for overhead fire sprinkler piping on level 8, tamper switch and flow switch satisfactorily tested for level 8.
|
FIR16-00075
| INSP-Sprinkler Rough-in/Hydro | 7/21/2016 | 7/22/2016 | 7/22/2016 1:22:52 PM | A | PASS |
|
|
Rough to cover inspection complete for level 9, hydrostatic test complete for overhead fire sprinkler piping on level 9, tamper switch and flow switch satisfactorily tested for level 9.
|
FIR16-00155
| INSP-Sprinkler Rough-in | 7/21/2016 | 7/22/2016 | 7/22/2016 1:16:42 PM | A | PASS |
|
|
Rough to cover inspection for hardlids located in the restrooms, 4th floor northside complete, hardlids approved for cover.
|
FIR16-00204
| INSP-Sprinkler Rough-in | 7/21/2016 | 7/22/2016 | 7/22/2016 11:05:09 AM | A | PASS |
|
|
24 hour air test for preaction system complete, 200 psi hydrostatic test for preaction system complete.
|
FIR15-00635
| INSP-Final Inspection | 7/20/2016 | 7/22/2016 | 7/22/2016 10:00:26 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR15-00561
| INSP-Sprinkler Rough-in | 7/21/2016 | 7/22/2016 | 7/22/2016 9:07:59 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping located on level 4 complete, overhead fire sprinkler piping located on level 4 approved for cover. Rough to cover inspection complete for overhead fire sprinkler piping located above the hardlids on level 1, overhead fire sprinkler piping located above the hardlids on level 1 approved for cover.
|
BLD16-01260
| FIRE-Final Inspection | 7/21/2016 | 7/22/2016 | 7/22/2016 8:35:44 AM | A | PASS |
|
|
No fire sprinkler modifications, fire alarm inspection complete (FIR permit was not attached in project related cases FIR16-00381), fire extinguishers are in common area's with current inspections tags. Final life fire safety inspection passed/complete.
|
FIR15-00795
| INSP-Final Inspection | 7/20/2016 | 7/22/2016 | 7/21/2016 5:23:15 PM | A | CANC |
|
|
Please call Jake when you are headed out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|