ELE19-02462
| Final | 7/22/2019 | 7/22/2019 | 7/22/2019 2:49:57 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jay Symonds...ok to final
|
ELE19-01529
| Conference | 7/19/2019 | 7/22/2019 | 7/22/2019 2:40:27 PM | P | PASS |
|
|
Looking for a status check on the work done so far. I am having minor finger surgery at 1:00 which should take about 1:00. Hoping to schedule conference after 3:00. Phone #: ###-#### Inspection requested via web by Ron MacCulloch...discussed connection to sub panel and make-up of switches and outlets...future rough-in inspection and final inspection requirements
|
ELE19-01529
| Electrical Rough-In | 7/22/2019 | 7/22/2019 | 7/22/2019 2:38:11 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ron MacCulloch... approval for column cover and ceiling cover only of patio addition
|
ELE19-02065
| Final | 7/22/2019 | 7/22/2019 | 7/22/2019 1:51:35 PM | P | FAIL |
|
|
Chad Vanorden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce.... 1) all receptacles within 6ft of sink shall have GFCI protection...unable to verify 240V outlet in breakroom 2) access for HVAC disconnect above grid shall have access...unable to verify
|
ELE19-01820
| Electrical Rough-In | 7/22/2019 | 7/22/2019 | 7/22/2019 1:03:21 PM | P | PASS |
|
|
Jeff- please call for access Phone #: ###-####... rough-in of new all-in one with overhead feed..ok
|
ELE19-01820
| Permanent Service | 7/22/2019 | 7/22/2019 | 7/22/2019 1:01:58 PM | P | PASS |
|
|
Jeff- please call for access Phone #: ###-####... p/s o/h new ok
|
ELE19-02558
| Final | 7/18/2019 | 7/22/2019 | 7/22/2019 10:14:20 AM | A | CANC |
|
|
Brittany Phone #: ###-####... Boise city ordinance requires a rough inspection of solar install before a final can be given job is complete...panels need removed and brought to ground level for inspection of listing and labelling...licensed electrician required to be on sight for inspection...spoke with Virginia solar rep and made aware of requirements 7/22/19 at 10AM
|
ELE19-02162
| Final | 7/22/2019 | 7/22/2019 | 7/22/2019 9:59:14 AM | A | PASS |
|
|
job complete...labelling, disconnect, and OCPD ok
|
ELE19-02162
| Electrical Rough-In | 7/19/2019 | 7/22/2019 | 7/22/2019 9:57:20 AM | A | PASS |
|
|
Taylor Barton is best contact Phone #: ###-#### Inspection requested via web by BRS Permitting....UL listed equipment and grounding verified
|
ELE19-02689
| Electrical Rough-In | 7/21/2019 | 7/22/2019 | 7/22/2019 9:30:57 AM | A | PASS |
|
|
Underground wire depth check. Please call me and give me 10 minutes to leave work. I''d like to chat about getting it to house. Phone #: ###-#### Inspection requested via web by Brad Downs... trench with UF wire to 2 outlet locations and garage wall...ok to cover
|
ELE19-02691
| Final | 7/19/2019 | 7/22/2019 | 7/22/2019 9:11:39 AM | A | PASS |
|
|
Mike Phone #: ###-####...complete ok to final
|
ELE19-00631
| Electrical Rough-In | 7/19/2019 | 7/22/2019 | 7/22/2019 9:08:48 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton... exterior soffit cans..2 locations...ok to cover
|
ELE19-02062
| Final | 7/19/2019 | 7/22/2019 | 7/22/2019 8:11:28 AM | A | FAIL |
|
|
power to sign. Phone #: ###-#### Inspection requested via web by Kendra Lanham.. 1) rough in inspection other then underground shall be schedule before final...material used and wiring methods need verified 2) access to panel to verify panel labelling and circuit rating ok
|