FIR19-00702
| INSP-Final Inspection | 7/21/2020 | 7/22/2020 | 7/22/2020 2:21:43 PM | P | CANC |
|
|
Inspection request cancelled per conversation with point of contact, fire alarm inspection did not get scheduled to coincide with fire sprinkler final.
Final inspection if hydro passes in AM. Coordinate with James. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00702
| INSP-Sprinkler Rough-in/Hydro | 7/21/2020 | 7/22/2020 | 7/22/2020 11:10:35 AM | A | FAIL |
|
|
Visible leaks plus pressure loss on riser gauges during hydro. Multiple areas that have 4.9K heads closer than 24 inches to heat registers in restrooms. Replace heads in areas where 5.6K should have been installed and 4.9K were put in place. Replace 5.6K head in apartment that should be a 4.9K. Dry sidewall head in south exterior room is farther than 6 inches from the deck, could not find any documentation allowing head to be outside the 4 too 6 inch measurement range. Provide head guards on heads under stairs, level 1.
Overhead hydro on all four floors. Call James before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00432
| INSP-Final Inspection | 7/22/2020 | 7/22/2020 | 7/22/2020 9:38:56 AM | A | FAIL |
|
|
Gas valve indicator light for valve trip during hood suppresion activation does not functioned, will need to be operational before next inspection. Added fryer is not compliant for clearance, fryer needs to be a minimum 6 inches under hood edge to be compliant. Provide splash guard between flat top cooker and fryer.
|
FIR20-00432
| INSP-Alarm Testing | 7/20/2020 | 7/22/2020 | 7/22/2020 9:36:23 AM | A | CANC |
|
|
Inspection was for final inspection, not alarm testing, this request is cancelled and the correct request will be generated.
SCREENED retirement building (could not answer about symtoms or interaction) // Leo Phone #: ###-####
|
BLD19-02201
| FIRE-Final Inspection | 7/22/2020 | 7/22/2020 | 7/22/2020 9:06:59 AM | P | PASS |
|
|
Final life fire safety inspection for area of work complete.
Kelly *screened* Phone #: ###-####
|
FIR20-00146
| INSP-Sprinkler Rough-in | 7/21/2020 | 7/22/2020 | 7/22/2020 9:06:28 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above east side exterior loading dock canopy complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Lonnie Greenfield
|