Inspections for the day of: Monday, July 23, 2001.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-00121 ELE-Aging Inspection7/23/20017/23/20017/23/2001 12:00:00 AM PASS
ok 7/23/2001 2:58:06 PM
ELE00-02514 Final7/19/20017/23/20017/23/2001 12:00:00 AMAFAIL
###-#### needs ko in fixture so box is accessible 7/23/2001 1:06:35 PM
ELE01-02457 Electrical Rough-In7/20/20017/23/20017/23/2001 12:00:00 AMAPART
###-#### walls in back and conference if questions on ceiling grid see JF 7/23/2001 10:08:59 AM
ELE01-02458 Electrical Rough-In7/20/20017/23/20017/23/2001 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 07/20/2001 at 13:49:15. Contact: ###-####. ufer is in stem wall south of job trailer ok 7/23/2001 9:28:42 AM
ELE01-02038 Electrical Rough-In7/20/20017/23/20017/23/2001 12:00:00 AMAPASS
guy wire on the mast Warren ###-#### ok 7/23/2001 10:19:34 AM
ELE01-01052 Final7/20/20017/23/20017/23/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 07/20/2001 at 17:54:21. Contact: ###-####. ok 7/23/2001 10:31:41 AM
ELE01-02381 Final7/23/20017/23/20017/23/2001 12:00:00 AMAFAIL
###-#### met with contractor no final corrections not made 7/23/2001 2:43:04 PM
ELE01-02470 Electrical Rough-In7/23/20017/23/20017/23/2001 12:00:00 AMPFAIL
###-#### cor. and do not cover posted called left message 370-16 box fill ? need info for wiremold boxes manufacture does not list romex too be installed in 500 wiremold if ? see JF 7/23/2001 2:46:55 PM
ELE01-01537 Electrical Rough-In7/23/20017/23/20017/23/2001 12:00:00 AMPPART
later pm ###-#### grid ceiling ALE area and walls in pharmacy 7/23/2001 3:49:36 PM
ELE01-00121 Final7/23/20017/23/20017/23/2001 12:00:00 AMPPASS
Added by Inspector: 315 On 7/23/2001 3:00:07 PM corrections made ok
ELE01-01987 Electrical Rough-In7/23/20017/23/20017/23/2001 12:00:00 AMPPART
wall cover wayne ###-#### ok
7/23/2001 1:02:21 PM
ELE01-01120 Final7/23/20017/23/20017/23/2001 12:00:00 AMPPASS
Jim ###-#### ok 7/23/2001 5:02:29 PM
ELE01-02380 Final7/23/20017/23/20017/23/2001 12:00:00 AMPFAIL
###-####083 cor. posted called 110-12 (a), 250-148, 300-10, 348-15, 334-10 shall secure MC within 12 inches of boxes and fixtures 7/23/2001 4:31:14 PM