Inspections for the day of: Tuesday, July 23, 2002.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01474 Electrical Rough-In7/22/20027/23/20027/23/2002 12:00:00 AMAPART
; Phone #: ###-#### basement ceiling ok 7/23/2002 11:51:27 AM
ELE02-01241 Final7/22/20027/23/20027/23/2002 12:00:00 AMAFAIL
; Phone #: ###-#### outlet for counter shall be on small appliance branch circuit, not living room circuit 7/23/2002 10:17:51 AM
ELE02-02238 Electrical Rough-In7/22/20027/23/20027/23/2002 12:00:00 AMAFAIL
###-#### need to meet with with 412 will post correction then called contractor 7/23/2002 11:52:53 AM
ELE02-02256 Temporary Service7/22/20027/23/20027/23/2002 12:00:00 AMAPASS
###-####
t/s o/h new ok 7/23/2002 2:47:39 PM
ELE02-01385 Rough-In Permanent Service7/22/20027/23/20027/23/2002 12:00:00 AMAFAIL
###-#### cor. posted met with owner 300.4 314.16, 20 300.14 250.104 11o.26 7/23/2002 1:00:24 PM
ELE02-01695 Final7/23/20027/23/20027/23/2002 12:00:00 AMAFAIL
meeting after 11:00 commercial project wired in romex, not allowed too be wired in romex called Jim Schmer 7/24/2002 2:35:06 PM
ELE02-01696 Electrical Rough-In7/23/20027/23/20027/23/2002 12:00:00 AMAPASS
meeting after 11:00 r/i ok 7/24/2002 2:35:27 PM
ELE02-02218 Final7/17/20027/23/20027/23/2002 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 07/17/2002 at 16:01:39. Contact: ###-####. see added p/s inspection 7/23/2002 5:42:39 PM
ELE02-01695 Final7/23/20027/23/20027/23/2002 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 07/23/2002 at 09:33:14. Contact: ###-####. see added inspection for 7/24/02 7/23/2002 6:31:13 PM
ELE02-01696 Electrical Rough-In7/23/20027/23/20027/23/2002 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 07/23/2002 at 09:34:52. Contact: ###-####. see added inspection for 7/24/02 7/23/2002 6:31:41 PM
ELE02-02238 Electrical Rough-In7/23/20027/23/20027/23/2002 12:00:00 AMPFAIL
cor. posted met contractor at job 110.26(F)(2), 314.20, and 16, 210.52 (A)(B),and 70 exception 7/23/2002 4:58:22 PM
ELE02-00760 Final7/23/20027/23/20027/23/2002 12:00:00 AMPPASS
###-#### call first for access ok 7/23/2002 3:39:45 PM
ELE02-02218 Permanent Service7/23/20027/23/20027/23/2002 12:00:00 AMPPASS
p/s o/h rec. ok
ELE01-03916 Rough-In Permanent Service7/22/20027/23/20027/23/2002 12:00:00 AMPPASS
scott; Phone #: ###-#### r/i ok

p/s o/h rec. ok 7/23/2002 4:20:28 PM