FIR04-00390
| INSP-Sprinkler Rough-in | 7/22/2004 | 7/23/2004 | 7/23/2004 12:00:00 AM | A | PART |
|
|
Inspection was for stub-out only. Plans show 8" but 6" was installed. Per conversation with Bill Alexander 6" will be OK as long as this is supported with revised hydraulic calculations. Stub-out is OK to bury. 7/23/2004 12:24:58 PM
|
FIR04-00393
| INSP-Sprinkler Rough-in | 7/22/2004 | 7/23/2004 | 7/23/2004 12:00:00 AM | A | PART |
|
|
Inspection was for stub-out only. Plans show 8" but 6" was installed. Per conversation with Bill Alexander 6" will be OK as long as this is supported with revised hydraulic calculations. Stub-out is OK to bury. 7/23/2004 12:24:51 PM
|
FIR04-00298
| INSP-Final Inspection | 7/22/2004 | 7/23/2004 | 7/23/2004 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled 7/23/2004 10:25:33 AM
|
BLD04-00055
| FIRE-Final Inspection | 7/23/2004 | 7/23/2004 | 7/23/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 7/23/2004 10:26:51 AM
|
FIR04-00415
| INSP-Final Inspection | 7/23/2004 | 7/23/2004 | 7/23/2004 12:00:00 AM | P | PASS |
|
|
kevin ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
MIS04-00189
| FIR-Final | 7/23/2004 | 7/23/2004 | 7/23/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled. No racking or storage bins have been provided for at the time of this final inspection, so I spoke to Kevin, contractor/superintendant, about the storage requirements. I reinforced his and Bill Alexander's conversation about the storage requirements, as follow: Owner will put racks on end with storage verticle to a maximum 6'-0" high and seal of the cutting table to prevent storage beneath the 80-ft/2 solid obstruction. Doing so will not require require fire sprinkler system review and required added sprinkler protection.
|
FIR04-00420
| INSP-Sprinkler Rough-in | 7/22/2004 | 7/23/2004 | 7/23/2004 12:00:00 AM | P | PART |
|
|
Hard lid areas ok to cover 7/23/2004 3:44:22 PM
|