Inspections for the day of: Monday, July 23, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00031 FIR-Aging Inspection7/23/20077/23/20077/24/2007 10:39:45 AM DONE
Work in progress.
FIR07-00280 INSP-Sprinkler Rough-in/Hydro7/20/20077/23/20077/23/2007 3:31:57 PMAPART
OH hydrostatic test completed satisfactory, need to provide seismic clearance for the 6" main as indicated on approved plans, one upright head is installed too low.
FIR07-00547 INSP-Final Inspection7/20/20077/23/20077/23/2007 3:05:56 PMAPASS
Fire sprinkler work passed final inspection, permit finaled.
FIR07-00377 INSP-Sprinkler Rough-in/Hydro7/20/20077/23/20077/23/2007 2:16:33 PMAPART
Defficiencies noted at the previous inspection are repaired, noted on stamped plan set areas okay for cover, discussed project scheduling.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro7/19/20077/23/20077/23/2007 1:10:10 PMAFAIL
Inspection for the first floor SE quad failed due to significant floor plan changes in comparison to approved drawings.
FIR07-00521 INSP-Sprinkler Rough-in/Hydro7/19/20077/23/20077/23/2007 1:06:33 PMAFAIL
Hydrostatic test failed due to start pressure below 200 psi, rooms added to the original TI area shall be shown on resubmittals, one overspaced head noted at the exit corridor SW corner, field modifications for the exit corridor fire sprinklers to be shown on as-built plans.
FIR07-00285 INSP-Sprinkler Rough-in7/20/20077/23/20077/23/2007 12:59:52 PMAFAIL
Inspection for the 1st floor hard lid ceilings only, pendent head at the NW entry does not meet requirements of NFPA 13 table 8.6.5.1.2, heads at the restrooms and the elevator equip. room are okay for cover.
FIR07-00574 INSP-Final Inspection7/18/20077/23/20077/23/2007 7:16:55 AMPCANC
Scheduled by a contractor via Hello! on 7/18/2007 at 5:12:38 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 23 2007 7:16AM.
BLD05-03359 FIRE-Final Inspection7/20/20077/23/20077/20/2007 12:00:00 AMADONE
greg- pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang