FIR09-00228
| INSP-Conference | 7/19/2012 | 7/23/2012 | 7/26/2012 6:54:54 AM | A | DONE |
|
|
Contact Mark for follow up.
|
FIR12-00364
| INSP-Final Inspection | 7/23/2012 | 7/23/2012 | 7/23/2012 3:49:01 PM | P | PASS |
|
|
Permit finaled
|
BLD12-00926
| FIRE-Final Inspection | 7/23/2012 | 7/23/2012 | 7/23/2012 3:26:12 PM | P | PASS |
|
|
life safety passed
|
BLD12-01043
| FIRE-Final Inspection | 7/20/2012 | 7/23/2012 | 7/23/2012 3:25:00 PM | A | PASS |
|
|
life safety passed
|
BLD12-01890
| FIRE-Final Inspection | 7/20/2012 | 7/23/2012 | 7/23/2012 11:12:56 AM | A | FAIL |
|
|
Provide city approved plans, provide a tagged fire extinguisher mounted as discussed and provide power to the tenant space so that the exit sign and emergency light can be tested.
|
BLD12-01122
| FIRE-Final Inspection | 7/20/2012 | 7/23/2012 | 7/23/2012 11:06:58 AM | A | FAIL |
|
|
Provide verification of racking permit for the existing racks that exceed 8' and provide verification that a racking permit is not required for the three new light duty 4' wide x 8' long by 10' high racks. Provide single action hardware on the southwest exterior main door. Remove the deadbolt from the door to the common (another tenant) restroom or provide verification from Tim that it can remain. Repair the two emergency lights that do not function. Daniel and I spoke about door hardware requirements if an "A" occupancy is applied for.
|