Inspections for the day of: Tuesday, July 23, 2013.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00695 INSP-Supply line flush7/23/20137/23/20137/23/2013 3:47:52 PMPPASS
The remaining underground is ok for cover and the flush for the two IBR's and the fire hydrant passed.
BLD13-01929 FIRE-Final Inspection7/23/20137/23/20137/23/2013 3:14:05 PMPFAIL
Remove or repair the non required exit sign and emergency light in the office area, provide single action lever type hardware and sticker for the main exit door
FIR13-00263 INSP-Sprinkler Rough-in7/22/20137/23/20137/23/2013 2:49:10 PMPPASS
ug for bldg 15 & 13 is ok to cover. See the city approved plans for locations.
FIR12-00582 FIR-Aging Inspection7/23/20137/23/20137/23/2013 2:47:51 PM NR
work is in progress
BLD13-00213 FIRE-Final Inspection7/23/20137/23/20137/23/2013 1:53:21 PMPFAIL
Repair the emergency lights and exit signs, remove the exit signs leading people to a room with no exit, provide fire extinguishers as discussed (none in tenant space at all)
FIR13-00204 INSP-Sprinkler Rough-in7/22/20137/23/20137/23/2013 1:18:20 PMAPASS
Todays inspection was to verify that the insulation had been repaired at the deck and was no longer obstructing the upright sprinkler heads. All areas had been repaired except for three locations. I will verify these three at the next rough-in inspection.
BLD13-01718 FIRE-Final Inspection7/22/20137/23/20137/23/2013 12:04:44 PMAFAIL
Provide approved single action hardware on the relocated door.
FIR12-00695 INSP-Sprinkler Rough-in7/22/20137/23/20137/23/2013 10:39:29 AMAPASS
See the city approved plans for location where underground supply piping can be covered.
BLD13-01047 FIRE-Final Inspection7/22/20137/23/20137/23/2013 10:34:04 AMAFAIL
Repair exit sign, get plan review approval for the exiting changes as discussed and get all of the fire extinguishers mounted as discussed.
BLD13-01786 FIRE-Final Inspection7/16/20137/23/20137/22/2013 12:00:00 AMACANC
mark Phone #: ###-#### // cancelled per Mark, will call back to reschedule 7/22/13 @ 11:55 -- leg