Inspections for the day of: Thursday, July 23, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00855 ELE-Aging Inspection7/23/20157/23/20157/24/2015 1:30:17 PM DONE
Waiting for contractor to call for final
ELE15-01609 Final7/23/20157/23/20157/23/2015 3:44:54 PMPPASS
Final inspection requested for today after 12 before 4pm when the store closes please call ###-#### if questions Phone #: ###-#### Inspection requested via web by Shane Lott Final ok
ELE15-01928 Final7/21/20157/23/20157/23/2015 3:20:30 PMPCANC
Matt is on site 7am - 3 pm. Phone #: ###-#### Inspection requested via web by Scott Campbell Needed rough in inspection
ELE15-01928 Electrical Rough-In7/23/20157/23/20157/23/2015 3:20:04 PMPPASS
Matt is on site 7am - 3 pm. Phone #: ###-#### Inspection requested via web by Scott Campbell Underground service feeders conduits and 3 pole bases rough in ok cover
ELE15-01913 Electrical Rough-In7/23/20157/23/20157/23/2015 2:51:04 PMPPASS
Underground Phone #: ###-#### Inspection requested via web by Bryan Atkins 4 1" conduit from school to portable classroom rough in ok cover
ELE14-00962 Electrical Rough-In7/23/20157/23/20157/23/2015 2:39:38 PMPPASS
Ken Phone #: ###-#### Shop rough in ok cover
ELE15-01597 Final7/23/20157/23/20157/23/2015 1:08:41 PMPPASS
Garage code is 0500 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
ELE15-01607 Final7/23/20157/23/20157/23/2015 12:46:42 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
ELE15-02274 Rough-In Permanent Service7/23/20157/23/20157/23/2015 12:24:47 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov 300.4- NM cable ran through bored holes that do not maintain 1 1/4" from framing surface shall be protected from physical damage. powder and under stair. 300.5- Under ground conduit shall be a minimum of 18" deep. 352.48- Joint at expansion joint and 90 degree elbow not square so cannot be seeded in very well. Already separating.
ELE15-01517 Electrical Rough-In7/22/20157/23/20157/23/2015 10:17:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Jim Williams Bath and offices walls and hardlid rough in ok cover
ELE15-01722 Final7/22/20157/23/20157/23/2015 9:44:07 AMAPASS
Dave Phone #: ###-#### Final ok
ELE15-01695 Final7/22/20157/23/20157/23/2015 9:19:38 AMAPASS
Access code is 6949, thx. Phone #: ###-#### Inspection requested via web by Stephen Kren Final ok
ELE15-02265 Electrical Rough-In7/22/20157/23/20157/23/2015 8:57:00 AMAPASS
Chad Phone #: ###-#### 2nd building to east north side. Bath and shower wall and hard lid rough in ok cover