ELE13-00855
| ELE-Aging Inspection | 7/23/2015 | 7/23/2015 | 7/24/2015 1:30:17 PM | | DONE |
|
|
Waiting for contractor to call for final
|
ELE15-01609
| Final | 7/23/2015 | 7/23/2015 | 7/23/2015 3:44:54 PM | P | PASS |
|
|
Final inspection requested for today after 12 before 4pm when the store closes please call ###-#### if questions Phone #: ###-#### Inspection requested via web by Shane Lott Final ok
|
ELE15-01928
| Final | 7/21/2015 | 7/23/2015 | 7/23/2015 3:20:30 PM | P | CANC |
|
|
Matt is on site 7am - 3 pm. Phone #: ###-#### Inspection requested via web by Scott Campbell Needed rough in inspection
|
ELE15-01928
| Electrical Rough-In | 7/23/2015 | 7/23/2015 | 7/23/2015 3:20:04 PM | P | PASS |
|
|
Matt is on site 7am - 3 pm. Phone #: ###-#### Inspection requested via web by Scott Campbell Underground service feeders conduits and 3 pole bases rough in ok cover
|
ELE15-01913
| Electrical Rough-In | 7/23/2015 | 7/23/2015 | 7/23/2015 2:51:04 PM | P | PASS |
|
|
Underground Phone #: ###-#### Inspection requested via web by Bryan Atkins 4 1" conduit from school to portable classroom rough in ok cover
|
ELE14-00962
| Electrical Rough-In | 7/23/2015 | 7/23/2015 | 7/23/2015 2:39:38 PM | P | PASS |
|
|
Ken Phone #: ###-#### Shop rough in ok cover
|
ELE15-01597
| Final | 7/23/2015 | 7/23/2015 | 7/23/2015 1:08:41 PM | P | PASS |
|
|
Garage code is 0500 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|
ELE15-01607
| Final | 7/23/2015 | 7/23/2015 | 7/23/2015 12:46:42 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
ELE15-02274
| Rough-In Permanent Service | 7/23/2015 | 7/23/2015 | 7/23/2015 12:24:47 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 300.4- NM cable ran through bored holes that do not maintain 1 1/4" from framing surface shall be protected from physical damage. powder and under stair. 300.5- Under ground conduit shall be a minimum of 18" deep. 352.48- Joint at expansion joint and 90 degree elbow not square so cannot be seeded in very well. Already separating.
|
ELE15-01517
| Electrical Rough-In | 7/22/2015 | 7/23/2015 | 7/23/2015 10:17:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Bath and offices walls and hardlid rough in ok cover
|
ELE15-01722
| Final | 7/22/2015 | 7/23/2015 | 7/23/2015 9:44:07 AM | A | PASS |
|
|
Dave Phone #: ###-#### Final ok
|
ELE15-01695
| Final | 7/22/2015 | 7/23/2015 | 7/23/2015 9:19:38 AM | A | PASS |
|
|
Access code is 6949, thx. Phone #: ###-#### Inspection requested via web by Stephen Kren Final ok
|
ELE15-02265
| Electrical Rough-In | 7/22/2015 | 7/23/2015 | 7/23/2015 8:57:00 AM | A | PASS |
|
|
Chad Phone #: ###-#### 2nd building to east north side. Bath and shower wall and hard lid rough in ok cover
|