BLD03-02061
| FIRE-Conference | 7/16/2015 | 7/23/2015 | 7/29/2015 12:46:51 PM | A | DONE |
|
|
Per conversation with owner he is going to meet with plan review
|
FIR15-00242
| INSP-Final Inspection | 7/23/2015 | 7/23/2015 | 7/23/2015 3:03:06 PM | P | PASS |
|
|
permit finaled
|
BLD14-03103
| FIRE-Final Inspection | 7/23/2015 | 7/23/2015 | 7/23/2015 2:00:02 PM | P | PART |
|
|
A temporary occupancy is being given until the 5" barrel on the fire hydrant is pointed the right way and correct fire dept access signage is provided.
|
FIR15-00415
| INSP-Sprinkler Rough-in/Hydro | 7/22/2015 | 7/23/2015 | 7/23/2015 1:58:42 PM | P | FAIL |
|
|
Stopped at job site and found that the pressure guage is at 185 psi which is below the required 200psi
|
FIR15-00195
| INSP-Final Inspection | 7/22/2015 | 7/23/2015 | 7/23/2015 12:06:06 PM | A | FAIL |
|
|
Missing coverage outside of the Pharmacy, missing strobe in the Pharmacy, overspaced strobe at the Bakery. No testing performed. Will need as-builts if notification is added in Bakery.
|
FIR15-00319
| INSP-Final Inspection | 7/21/2015 | 7/23/2015 | 7/23/2015 10:56:19 AM | A | FAIL |
|
|
Flow switches failed to operate. Need soffits on exposed pipe in storage rooms
|
FIR15-00499
| INSP-Final Inspection | 7/22/2015 | 7/23/2015 | 7/23/2015 10:54:25 AM | A | FAIL |
|
|
The fire sprinkler flow switches failed to operate. all other devices tested ok.
|
FIR15-00379
| INSP-Sprinkler Rough-in | 7/22/2015 | 7/23/2015 | 7/23/2015 10:50:49 AM | A | PASS |
|
|
The piping in the three focus rooms is ok to cover
|
BLD15-00488
| FIRE-Final Inspection | 7/21/2015 | 7/23/2015 | 7/23/2015 10:35:01 AM | A | FAIL |
|
|
Life safety will be ok to pass when the project related fire alarm and sprinkler permits have been finaled and soffits bult around the exposed pipe in the storage closets
|
FIR14-00815
| INSP-Final Inspection | 7/23/2015 | 7/23/2015 | 7/23/2015 10:04:55 AM | P | CANC |
|
|
This is a final inspection for 3/1, 2/2, and 3/2. The contact is Mark. Thanks. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR15-00324
| INSP-Sprinkler Rough-in | 7/22/2015 | 7/23/2015 | 7/23/2015 9:06:10 AM | A | PASS |
|
|
See the city approved drwings for new area with todays date where piping is ok to cover.
|