Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02998 ELE-Aging Inspection7/23/20187/23/20187/24/2018 3:32:34 PM FAIL
Waiting on contractor to schedule
ELE18-02737 Permanent Service7/23/20187/23/20187/23/2018 4:19:02 PMPFAIL
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Contractor to verify AFC
ELE18-02738 Permanent Service7/23/20187/23/20187/23/2018 4:17:48 PMPPASS
All main rated at 65K. p/s u/g rec ok
ELE18-02739 Permanent Service7/23/20187/23/20187/23/2018 4:16:49 PMPFAIL
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Due to changing of transformer feeding service main disconnect not rated for new available fault current. Shall update.
ELE18-02231 Permanent Service7/23/20187/23/20187/23/2018 4:14:42 PMPPASS
Contact to verify available fault current reating of main fuses. Due to I have not seen one under 100k will pass.
p/s u/g rec ok
ELE18-02736 Permanent Service7/23/20187/23/20187/23/2018 4:12:22 PMPFAIL
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Over 46K available at terminal of existing main breaker. Will create change order to correct.
ELE18-02735 Permanent Service7/23/20187/23/20187/23/2018 4:10:17 PMPPASS
Has 65k rated main. p/s u/g rec ok
ELE18-02734 Permanent Service7/23/20187/23/20187/23/2018 4:08:32 PMPPASS
Has 65K rated main. p/s u/g rec ok
ELE18-02731 Permanent Service7/21/20187/23/20187/23/2018 4:06:22 PMPPASS
Please try to make this as late as 3 or 4PM. Phone #: ###-#### Inspection requested via web by Kelly Tarter
Residential service existing has been upgraded in recent past. p/s u/g rec ok
ELE18-02732 Permanent Service7/21/20187/23/20187/23/2018 4:04:32 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kelly Tarter
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Device on order.
ELE18-02733 Permanent Service7/21/20187/23/20187/23/2018 4:03:25 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kelly Tarter
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Device on order.
ELE18-02706 Conference7/23/20187/23/20187/23/2018 2:47:25 PMPDONE
Luke Phone #: ###-####
Discussed required items that shall be installed to code.
Verify minimum 20 amp appliance circuits are present. Kitchen receptacle layout complies.
Bathroom receptacles shall have a dedicated 20 amp circuit.
Required wall receptacles for kitchen area, living, dining.
Add smoke detectors for main floor and basement.
Grounding type receptacles installed on ungrounded circuits shall have GFCI protection or change to 2 wire receptacles. No AFCI required no work done in beds.
6-3 in basement shall be removed, owner eventually wants range in basement. Not zoned or designed for range in basement.
AC unit is new and shall provide a minimum of 3' from gas meter. A receptacle outlet shall be located with in 25' of AC unit. All wiring in garage that has been installed by prior owner or tenant shall be remove due to none is installed to NEC.
Receptacle exists in front of house shall have GFCI protection.
ELE17-02862 Electrical Rough-In7/23/20187/23/20187/23/2018 2:06:12 PMPPASS
Drop ceilings 401, 402 , 403 , 404 , 405 , 406 , 407 , 408 , 410 , 417 ,418 and Phone #: ###-#### Inspection requested via web by Tom Betty
401, 410 not ready, rest of rooms noted and added 419 drop lid rough in ok cover
ELE18-02369 Electrical Rough-In7/23/20187/23/20187/23/2018 1:01:27 PMPPASS
Joey Phone #: ###-####
Note: If an inspection is needed time shall be provided to complete and inspect before cover. Concrete encased electrode rough in ok cover
ELE18-02369 Electrical Rough-In7/18/20187/23/20187/23/2018 10:03:16 AMAPASS
Please call Joey Campbell @ ###-#### 20 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Underslab conduits to east of electrical room rough in ok cover
ELE18-02506 Electrical Rough-In7/23/20187/23/20187/23/2018 9:02:09 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
Pediatric area walls rough in ok cover