ELE12-02998
| ELE-Aging Inspection | 7/23/2018 | 7/23/2018 | 7/24/2018 3:32:34 PM | | FAIL |
|
|
Waiting on contractor to schedule
|
ELE18-02737
| Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 4:19:02 PM | P | FAIL |
|
|
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Contractor to verify AFC
|
ELE18-02738
| Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 4:17:48 PM | P | PASS |
|
|
All main rated at 65K. p/s u/g rec ok
|
ELE18-02739
| Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 4:16:49 PM | P | FAIL |
|
|
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Due to changing of transformer feeding service main disconnect not rated for new available fault current. Shall update.
|
ELE18-02231
| Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 4:14:42 PM | P | PASS |
|
|
Contact to verify available fault current reating of main fuses. Due to I have not seen one under 100k will pass. p/s u/g rec ok
|
ELE18-02736
| Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 4:12:22 PM | P | FAIL |
|
|
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Over 46K available at terminal of existing main breaker. Will create change order to correct.
|
ELE18-02735
| Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 4:10:17 PM | P | PASS |
|
|
Has 65k rated main. p/s u/g rec ok
|
ELE18-02734
| Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 4:08:32 PM | P | PASS |
|
|
Has 65K rated main. p/s u/g rec ok
|
ELE18-02731
| Permanent Service | 7/21/2018 | 7/23/2018 | 7/23/2018 4:06:22 PM | P | PASS |
|
|
Please try to make this as late as 3 or 4PM. Phone #: ###-#### Inspection requested via web by Kelly Tarter Residential service existing has been upgraded in recent past. p/s u/g rec ok
|
ELE18-02732
| Permanent Service | 7/21/2018 | 7/23/2018 | 7/23/2018 4:04:32 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kelly Tarter 110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Device on order.
|
ELE18-02733
| Permanent Service | 7/21/2018 | 7/23/2018 | 7/23/2018 4:03:25 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kelly Tarter 110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Device on order.
|
ELE18-02706
| Conference | 7/23/2018 | 7/23/2018 | 7/23/2018 2:47:25 PM | P | DONE |
|
|
Luke Phone #: ###-#### Discussed required items that shall be installed to code. Verify minimum 20 amp appliance circuits are present. Kitchen receptacle layout complies. Bathroom receptacles shall have a dedicated 20 amp circuit. Required wall receptacles for kitchen area, living, dining. Add smoke detectors for main floor and basement. Grounding type receptacles installed on ungrounded circuits shall have GFCI protection or change to 2 wire receptacles. No AFCI required no work done in beds. 6-3 in basement shall be removed, owner eventually wants range in basement. Not zoned or designed for range in basement. AC unit is new and shall provide a minimum of 3' from gas meter. A receptacle outlet shall be located with in 25' of AC unit. All wiring in garage that has been installed by prior owner or tenant shall be remove due to none is installed to NEC. Receptacle exists in front of house shall have GFCI protection.
|
ELE17-02862
| Electrical Rough-In | 7/23/2018 | 7/23/2018 | 7/23/2018 2:06:12 PM | P | PASS |
|
|
Drop ceilings 401, 402 , 403 , 404 , 405 , 406 , 407 , 408 , 410 , 417 ,418 and Phone #: ###-#### Inspection requested via web by Tom Betty 401, 410 not ready, rest of rooms noted and added 419 drop lid rough in ok cover
|
ELE18-02369
| Electrical Rough-In | 7/23/2018 | 7/23/2018 | 7/23/2018 1:01:27 PM | P | PASS |
|
|
Joey Phone #: ###-#### Note: If an inspection is needed time shall be provided to complete and inspect before cover. Concrete encased electrode rough in ok cover
|
ELE18-02369
| Electrical Rough-In | 7/18/2018 | 7/23/2018 | 7/23/2018 10:03:16 AM | A | PASS |
|
|
Please call Joey Campbell @ ###-#### 20 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell Underslab conduits to east of electrical room rough in ok cover
|
ELE18-02506
| Electrical Rough-In | 7/23/2018 | 7/23/2018 | 7/23/2018 9:02:09 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Pediatric area walls rough in ok cover
|