Inspections for the day of: Tuesday, July 23, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01708 ELE-Aging Inspection7/23/20197/23/20197/23/2019 3:10:16 PM FAIL
Waiting on contractor to schedule
ELE19-01296 Final7/22/20197/23/20197/23/2019 2:27:33 PMPFAIL
Please call Jim for access ###-#### Phone #: ###-#### Inspection requested via web by William Andrews
110.3- Open ground at receptacle in basement near fireplace.
210.8- All 15 and 20 amp 120 volt receptacle outlets located in unfinished basement area shall have GFCI protection. Unable to test all bathroom receptacles because some not working.
210.70- Neither switch located at stairway would operate light above.
300.15- all cables shall terminate in a box. Basement UF hanging.
410.10(A)- Rear patio light not mounted on surface so water will not enter wiring in box or wall.
* Remove all abandoned 2 wire receptacles for patching.
ELE19-02670 Electrical Rough-In7/22/20197/23/20197/23/2019 1:27:25 PMPFAIL
Open ceiling inspection Phone #: ###-#### Inspection requested via web by Steven Ragan 300.11(B)- Support wires used to support cables shall be secured at both ends.
300.15- All cables shall terminate in a box. (2). 314.25- All boxes shall have covers. 12"x12".
330.30- MC cable supports shall not exceed 6' intervals and shall be secured with in12" of a box. 410.36(B)- Luminaires mounted to ceiling grid shall be secured to ceiling grid by machanical means or by approved clips.
ELE19-02603 Final7/22/20197/23/20197/23/2019 10:43:43 AMAPASS
Final four service upgrade. Phone #: ###-#### Inspection requested via web by Casey Fouts
Final ok
ELE19-02635 Electrical Rough-In7/23/20197/23/20197/23/2019 10:01:17 AMAPASS
TI space is on the NW corner on the first floor with one new wall to inspect.
Please call with any concerns or questions. Phone #: ###-#### Inspection requested via web by Jim Noll
Wall rough in work room ok cover
ELE19-01601 Final7/22/20197/23/20197/23/2019 9:10:33 AMAPASS
Install 2 wall signs. All Primary power by others Phone #: ###-#### Inspection requested via web by Ken Olsen
Listing and disconnecting means confirmed. Final ok
ELE19-02247 Electrical Rough-In7/22/20197/23/20197/23/2019 7:46:23 AMACANC
Requesting 9:00 am inspection time. Phone #: ###-#### >> Inspection requested via web by Ken Olsen Inspection cancelled from web by: Ken Olsen