Inspections for the day of: Wednesday, July 24, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00582 INSP-Sprinkler Rough-in/Hydro7/23/20027/24/20027/24/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 07/23/2002 at 11:40:05. Contact: ###-####. hydro okay; will need alarm plans for new tamper; heads obstructed by lights; 4 ft wide obstruction requires head underneath it; pressure switch on dry valve needs supervised switch 7/24/2002 10:41:10 AM
BLD00-02574 FIRE-Sprinkler Rough-in7/23/20027/24/20027/24/2002 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 07/23/2002 at 13:04:51. Contact: ###-####. wrong type inspection; final okay 7/24/2002 10:23:05 AM
FIR02-00209 INSP-Sprinkler Rough-in7/23/20027/24/20027/24/2002 12:00:00 AMAPART
###-#### okay to cover ceiling 7/24/2002 9:00:07 AM
BLD01-00942 FIRE-Final Inspection7/23/20027/24/20027/24/2002 12:00:00 AMANR
tim ###-####
BLD01-00967 FIRE-Final Inspection7/23/20027/24/20027/24/2002 12:00:00 AMAFAIL
tim ###-#### need resubmittals for horn circuits; extinguishers; knox box keys; test horn circuits 7/24/2002 5:02:09 PM
BLD01-01944 FIRE-Sprinkler Rough-in7/24/20027/24/20027/24/2002 12:00:00 AMAPASS
okay to cover ceiling; insulation okay
FIR01-00311 INSP-Final Inspection7/24/20027/24/20027/24/2002 12:00:00 AMAPASS
FIR01-00520 INSP-Final Inspection7/24/20027/24/20027/24/2002 12:00:00 AMAPASS
BLD00-02574 FIRE-Final Inspection7/24/20027/24/20027/24/2002 12:00:00 AMAPASS
BLD02-00698 FIRE-Final Inspection7/24/20027/24/20027/24/2002 12:00:00 AMPFAIL
TERRY; Phone #: ###-#### extinguisher 7/24/2002 2:13:22 PM