ELE03-01385
| Final | 7/23/2003 | 7/24/2003 | 7/24/2003 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 7/23/2003 at 8:33:54 AM. Contact: ###-####. cor. posted called 314.16 outlet end of peninsular counter , also put wires around screw terminals clockwise left message 7/24/2003 1:46:12 PM
|
ELE03-01906
| Temporary Service | 7/23/2003 | 7/24/2003 | 7/24/2003 12:00:00 AM | A | PASS |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
t/s u/g new ok 7/23/2003 3:29:38 PM
|
ELE03-02238
| Temporary Service | 7/23/2003 | 7/24/2003 | 7/24/2003 12:00:00 AM | P | FAIL |
|
|
dan- ###-#### cell cor. posted called left message 110.3(B) use manufactures breakers 527.6 (B) (1) gfci for 220 volt recepts 7/24/2003 3:37:57 PM
|
ELE02-03943
| Electrical Rough-In | 7/24/2003 | 7/24/2003 | 7/24/2003 12:00:00 AM | P | PART |
|
|
allen; Phone #: ###-#### Internet Inspection Request from: Annette Moore u/g for a/c 7/24/2003 2:56:09 PM
|
ELE03-01168
| Final | 7/23/2003 | 7/24/2003 | 7/24/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/23/2003 at 9:13:55 AM. Contact: ###-####. ok 7/24/2003 2:55:47 PM
|