Inspections for the day of: Monday, July 24, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00263 FIR-Aging Inspection7/24/20067/24/20067/26/2006 10:41:46 AM NR
Per Tom he is waiting for a window of opportunity to do the work.
FIR06-00510 INSP-Sprinkler Rough-in7/24/20067/24/20067/24/2006 4:07:04 PMPPASS
Underground piping is ok to cover.
FIR05-00693 INSP-Sprinkler Rough-in7/21/20067/24/20067/24/2006 4:03:28 PMPPASS
See approved plans for ceiling areas that are ok to cover.
FIR06-00272 INSP-Final Inspection7/24/20067/24/20067/24/2006 3:56:13 PMPCANC
bill ###-####
FIR05-00713 INSP-Final Inspection7/24/20067/24/20067/24/2006 3:55:08 PMPCANC
Scheduled by a contractor via Hello! on 7/24/2006 at 9:26:31 AM. Contact: ###-####.
FIR06-00440 INSP-Final Inspection7/24/20067/24/20067/24/2006 3:31:16 PMPFAIL
Provide approval notes that accompany the approved plans, tenting is inadequate and needs modified in several locations, provide additional hangers on the 1 1/2" main in the west end of the basement, sidewall heads in the garage appear to be overspaced and provide as-built drawings and hydraulic calculations that include all of the piping changes and hydraulic calculation changes including the slope from the street to the riser
FIR06-00218 INSP-Sprinkler Rough-in/Hydro7/24/20067/24/20067/24/2006 3:28:31 PMPPASS
Hydro test of the FDC passed.
FIR06-00513 INSP-Supply line flush7/24/20067/24/20067/24/2006 3:14:10 PMPPART
Inspection was for supply line cover not a flush. The stubout and the first four lengths of supply piping are ok to cover.
BLD05-02593 FIRE-Sprinkler Rough-in7/21/20067/24/20067/24/2006 3:01:26 PMAFAIL
Provide approval notes that accompany the approved plans, tenting is inadequate and needs modified in several locations, provide additional hangers on the 1 1/2" main in the west end of the basement, sidewall heads in the garage appear to be overspaced and provide as-built drawings and hydraulic calculations that include all of the piping changes and hydraulic calculation changes including the slope from the street to the riser
FIR06-00389 INSP-Final Inspection7/21/20067/24/20067/24/2006 1:36:15 PMAFAIL
Ok to final when the 9th floor trouble on the facp has been fixed.
BLD05-02089 FIRE-Conference7/21/20067/24/20067/24/2006 1:01:22 PMADONE
I went over the life safety items with Mike.
FIR05-00644 INSP-Sprinkler Rough-in7/21/20067/24/20067/24/2006 12:33:06 PMAPASS
The east half of the first floor is ok to cover. I also inspected the concealed pockets in the room entry ways and verified that they are indeed noncombustible.
BLD06-00531 FIRE-Final Inspection7/24/20067/24/20067/24/2006 10:37:52 AMAPASS
Life safety finaled
FIR06-00509 INSP-Final Inspection7/24/20067/24/20067/24/2006 8:24:36 AMAFAIL
No access and no answer at the contact phone number