FIR05-00536
| INSP-Sprinkler Rough-in | 7/24/2007 | 7/24/2007 | 7/24/2007 4:51:48 PM | P | PASS |
|
|
See the city approved plans for the sprinkler piping that is ok to cover on the second floor north tower corridor.
|
FIR06-00011
| INSP-Alarm Testing | 7/24/2007 | 7/24/2007 | 7/24/2007 4:50:11 PM | P | DONE |
|
|
See the city approved plans for items in the penthouse that have been tested. The heat detectors located in the elevator equipment room need to be located at the ceiling as per NFPA 72 5.6.3.2 and the heat detectors located near the sprinklers under the obstructions shall be located under the obstructions as well.
|
MIS07-00153
| FIR-Final | 7/23/2007 | 7/24/2007 | 7/24/2007 2:27:09 PM | A | PART |
|
|
A temporary occupancy was given for the office area only. The warehouse area and use of the racks is not included. The owner is still working on getting the racking permit and the sprinkler work has been scheduled.
|
BLD07-00670
| FIRE-Final Inspection | 7/23/2007 | 7/24/2007 | 7/24/2007 2:24:30 PM | A | PASS |
|
|
fire life safety passed
|
BLD07-00669
| FIRE-Final Inspection | 7/23/2007 | 7/24/2007 | 7/24/2007 2:23:55 PM | A | PASS |
|
|
fire life safety passed.
|
FIR06-00708
| INSP-Final Inspection | 7/23/2007 | 7/24/2007 | 7/24/2007 2:22:08 PM | A | FAIL |
|
|
See the city approved plans for the items tested. Still need to perform elevator recall, provide covers and remove tape from a/v's, need as-built plans and map at facp, provide signage at the standpipe control vavles.
|
FIR07-00237
| INSP-Final Inspection | 7/23/2007 | 7/24/2007 | 7/24/2007 2:18:52 PM | A | FAIL |
|
|
See the city approved plans for location where an a/v needs to be added. Also three a/v's need to be relocated or candella increased. The interconnection between the NAC and the FACP needs tested. Also the a/v's have not been sounded yet.
|